© Caleffi 11236_iSolar_Plus.mon
us.ind
d
|
20
9 10
VBus
S1
S2
S3
R1
R2
System layout 6
The controller calculates the temperature differences
between collector sensor S1 and tank sensors S2 and S3. If
the differences are larger than or identical to the adjusted
switch-on temperature differences (DT1O / DT2O), the
solar pumps will be operated by relay 1 and / or relay 2,
and the respective tank will be loaded until the switch-off
temperature differences (DT1F / DT2F) or the maximum
Arr 6
Tank 1
Tank 2
S4
Display Channels
Channel
Description
Terminal
Page
COL
x
Temperature collector
S1
37
TST1
x
Temperature tank 1 bottom
S2
37
TST2
x
Temperature tank 2 bottom
S3
37
S4
x
Temperature sensor 4
S4
37
n1 %
x
Pump speed R1
R1
38
n2 %
x
Pump speed R2
R2
38
h P1
x
Operating hours R1
R1
38
h P2
x
Operating hours R2
R2
38
TIME
x
Time
-
34
tank temperatures (S1MX / S2MX) are reached. The priority
logic causes priority loading of the selected tank (PRIO), if
possible. Loading both tanks simultaneously is possible as
well (PRIO = 0).
Sensor S4 can optionally be connected for measurement
purposes or used as reference sensor for the tank emer-
gency shutdown option (OSEM).