© Caleffi 11236_iSolar_Plus.mon
us.ind
d
|
10
∆
T control for the heat exchange between 2 tanks
DT3O:
Switch-on temperature diff.
Adjustment range: 2.0 ... 40.0°Ra
[1.0 ... 20.0 K]
in steps of 1 °Ra [0.5 K]
Factory setting: 12.0°Ra
[6.0 K]
DT3F:
Switch-off temperature diff.
Adjustment range: 1.0 ... 39.0°Ra
[0.5 ... 19.5 K]
in steps of 1 °Ra [0.5 K]
Factory setting: 8.0°Ra
[4.0 K]
Reference sensors for this function are S3 and S4.
In system layout 2 the controller is equipped with an addi-
tional differential control for heat exchange between two
tanks. The basic differential function is adjusted using the
switch-on (DT3O) and switch-off (DT3F) temperature
differences.
When the temperature difference exceeds the switch-on
temperature difference, relay 2 switches on. If the tempe-
rature difference then falls below the adjusted switch-off
temperature difference, relay 2 switches off.
Note:
The switch-on temperature difference must be
at least 1 °Ra [0.5 K] higher than the switch-off
tempe rature difference.
DT3S:
Nominal temperature difference
Adjustment range: 3.0 ... 60.0 °Ra
[1.5 ... 30.0 K]
in steps of 1 °Ra [0.5 K]
Factory setting: 20.0 °Ra
[10.0 K]
RIS3:
Rise
Adjustment range:
2 ... 40 °Ra
[1 ... 20 K]
in steps of 2 °Ra [1 K]
Factory setting: 4 °Ra [2 K]
Pump speed control
A relative minimum pump speed can be allocated to the
output R2 via the adjustment channel n2MN.
n2MN:
Pump speed control
Adjustment range:
30 ... 100
in steps of 5 %
Factory setting: 30
Note:
When loads which are not speed-controlled (e.g.
valves) are used, the value must be set to 100 % in
order to deactivate pump speed control.
Minimum pump speed
When the switch-on temperature difference is reached, the
pump is activated at full speed for 10 seconds. Then, the speed
is reduced to the minimum pump speed value (n2MN).
If the temperature difference reaches the adjusted nominal
temperature difference (DT3S), the pump speed increases by
one step (10 %). If the difference increases by the adjustable rise
value, the pump speed increases by 10 % respectively until the
maximum pump speed of 100 % is reached. The response of
the controller can be adapted via the parameter RIS3.
Note:
The nominal temperature difference must be
at least 1 °Ra [0.5 K] higher than the switch-on
tempe rature difference.
Note:
For pump speed control of the heat exchange
pump, the operation mode of relay 2 (MAN2)
must be set to Auto.
System-specific functions
The following adjustments are used for the specific function
in system layout 2.