CL-B101D40PS Manual (d0096)
Page 1
Smart 101 segment, 4 digit LED Tricolor or Mono-color
digital bargraph controller with Programmable Scale
Factor input signal scaling and four fully programmable
set points in a switchboard style case for
monitoring, measurement, and control applications.
0.56” LEDs
•
External transmitters or signal conditioners can be eliminated by
direct connection of the sensor output to more than
40 Plug-in Input Signal Conditioners that include:
– AC/DC Current
– Pressure
– Resistance
– AC/DC Voltage
– Process
– Temperature
– Load Cell
– Prototype
– 4 to 20 mA
•
Optional isolated 16 bit analog output. User or factory scalable to 4
to 20 mA, 0 to 20 mA or 0 to 10 V across any desired digital span
from ± one count to the full scale range of – 1999 to 9999 (12000
counts).
•
A Programmable Tricolor (Red-Green-Orange) or mono color (red or
green), 101 segment high brightness bargraph.
•
Red 4-digit LED display with a range of -1999 to 9999
(12000 counts). Optional green digital display.
•
Front panel LED annunciators provide indication of setpoint status.
•
Two 9 Amp Form C, and two 4 Amp Form A or 4 x 4 Amp Form A
relays available.
•
Auto-sensing AC/DC power supply. For voltages between
85-265 V AC / 95-300 V DC (PS1) or 18-48 V AC / 10-72 V DC
(PS2).
•
24 V DC excitation is available to power external 4/20mA
transmitters and 5 or 10 V DC excitation is available for
resistance bridge type sensors.
•
Provision to connect an external programming lockout switch.
•
Provision for external DIM switch to reduce the brightest
display setting by 50%.
•
Automatic intelligent averaging, smooths noisy signals while
providing a fast display response to real level changes.
General Features
Specifications
• The bargraph can display, full
scale, any desired portion of
the digital reading.
• Setpoint 1 has delay-on-make
and delay-on-break plus
a special “pump on pump
off” mode that creates a
Hysteresis Band between SP1
and SP2.
Software Features
•
Four programmable setpoints
with adjustable Hysteresis.
•
Bargraph center zero function.
• Relay activation can be select
-
ed to occur above (hi) or below
(Lo) each setpoint.
• Digital display blanking.
• Decimal point setting.
• Four-level brightness control
LEOPARD
FAMILY
Input Specs: ������������������Depends on Input signal conditioner
A/D Converter: ��������������14 bit single slope
Accuracy: ����������������������±(0�05% of r 2 counts)
Temp. Coeff�: �����������������100 ppm/°C (Typical)
Warm up time: ���������������2 minutes
Conversion Rate: ����������10 conversions per second (Typical)
Digital Display: ��������������4 digit 0.56" LED red (std), green (optn)
Range –1999 to 9999 counts�
Bargraph Display: ���������101 segment 235º circular red (standard),
Green (optional) or tricolor (optional) LED�
Polarity: �������������������������Assumed positive� Displays – negative
Decimal Selection: ��������Front panel button selectable, X•X•X•X•
Positive Overrange: ������Bargraph and top segments of digital display
flash�
Negative Overrange: ����First segment of bargraph and bottom seg-
ments of digital display flash�
Relay Output: ����������������Two 9 Amp Form C relays, two 4 Amp Form
A relays or
4 x 4 Amp Form A relays
Analog Output: �������������Isolated 16 bit user scalable mA or V
OIC (mA out) ��������������4-20 mA @ 0 to 500٠max loop resistance
OIV (volts out) �������������� 0-10 V DC @ 500 ٠or higher resistance
Power Supply: ���������������AC/DC Auto sensing wide range supply
PS1 (std) ��������������������85-265 VAC / 95-300 VDC, 50-400Hz 4.2W
PS2 �����������������������������18-48 VAC / 10-72 VDC, 50-400Hz 4�2W
Operating Temp�: ����������0 to 50°C
Storage Temp: ���������������–20°C to 70°C
Relative Humidity: ��������95% (non condensing)
Case Dimensions: ��������Bezel (4.48"x4.48") 113.8x113.8mm
Depth behind bezel (4.23") 107.46 mm
Plus (0�48”) 12�24 mm for connectors
Weight: ���������������������������16 oz�, 1lb 4 oz when packed
Table of Contents
Bargraph Center Point Display Mode Selection . . 7
Bargraph Color Programming Mode . . . . . . 10
Case Dimensions. . . . . . . . . . . . . . . . . . . . . . . 8
Component Layout . . . . . . . . . . . . . . . . . . . . 12
Connector Pinouts . . . . . . . . . . . . . . . . . .11-12
Controls and Indicators . . . . . . . . . . . . . . . . . 2
Decimal Point and Brightness Selection . . . . 6
Digital Span Selection for Bargraph Display . 6
Programming Conventions . . . . . . . . . . . . . . . 2
Setpoint Setting & Relay Conf. Mode . . . .9-10
Software Features . . . . . . . . . . . . . . . . . . . . . . 1
Software Logic Tree . . . . . . . . . . . . . . . . . . . . 3
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . 1
Successive Digital Rescaling. . . . . . . . . . . . . . . . . . . .5
Two Point Analog Range Setting & Calibration. . . 8
Digital Span Selection for Analog Range Output . 7
Functional Diagram. . . . . . . . . . . . . . . . . . . . 11
General Features. . . . . . . . . . . . . . . . . . . . . . . 1
I-Series Input Signal Conditioning Modules . .13-15
Input Module Calibration Procedures . . . . . 17
Input Module Component Glossary . . . . . . . 16
Ordering Information. . . . . . . . . . . . . . . . . . . 19
Pin Descriptions . . . . . . . . . . . . . . . . . . . . . . 11