CL-B101D40PS Manual (d0096)
Page 3
Software Logic Tree
The
CL-B101D40PS
is an intelligent bargraph meter with a hier-
archical software structure designed for easy programming and
operation, as shown below in the software logic tree.
Peak
Reset
PEAK
Reset
VALY
Valley
[orAn]
[rEd]
NOTE: Will only
appear if a tricolor
display is installed
[orAn]
[rEd]
[orAn]
[rEd]
[orAn]
[rEd]
[orAn]
[rEd]
BARGRAPH COLOR
PROGRAMMING MODE
See Page 9
Tricolor Bargraph
The tri-color bargraph is designed
like a traffic light, to display either
red, orange or green, but only one
color at a time. The color to be
displayed is selected in two ways.
The first step is to select the color
to be displayed when the bar is
“below” whichever set point is set to
the lowest position.
The second step is to select the
color to be displayed when the bar
is above each specific setpoint,
regardless of the order or position
to which the set points are set.
However, if two or more setpoints
with differently specified colors are
positioned at the same set point
value, the color specified for the set
point with the highest identifying
number will be displayed. When
setpoints are set to the same value,
the SP4 color overrides the SP3
color, the SP3 color overrides the
SP2 color, and the SP2 color
overrides the SP1 color.
[rLYS] (h) High
the relay
energizes
when the
setpoint is
exceeded.
(L) Low
the relay
energizes below
the setpoint.
(–) Disabled
the relay will be
diabled and
removed from
the menu.
Pump On Pump Off
When PUM is selected ON,
and SP2 is set at a value
higher than SP1, the SP1
relay will operate in
a special "pump on pump off"
Hysteresis mode. SP2 acts
as the upper limit and SP1
acts as the lower limit of the
Hysteresis Band.
For filling applications, rLYS
should be set to LhLh. SP1 will
then activate for inputs less than
the SP1 setpoint, and remain
ON until the SP2 setpoint is
reached.
For emptying applications,
rLYS should be set to hhhh.
SP1 will then activate for inputs
greater than the SP2 setpoint,
and remain ON until the SP1
setpoint is reached.
Operational Display
MAIN MENU
PEAK & VALLEY
VIEW & RESET
BRIGHTNESS AND
SETPOINT VIEW MODE
Bargraph Center Point
Display Selection (cto)
This branch will
only appear if
the analog
output option
is installed
Back to
Operational
Display
Digital Display
ON/OFF
Selection (diSP)
Sub-menu MODE
Calibration
Input
Calibration
Output
Calibrate Analog
Output Lo
Calibrate Analog
Output Hi
Select the Digital
Reading at which
the Analog Output
Hi (chi) will occur
Select the Digital
Reading at which
the Analog Output
Lo (cLo) will occur
This branch will only
appear if the analog
output option
is installed
DIGITAL SPAN SELECTION
FOR ANALOG RANGE OUTPUT
See Page 6
DIGITAL DISPLAY ON/OFF
See Page 6
BARGRAPH CENTER POINT
DISPLAY MODE SELECTION
See Page 6
TWO POINT ANALOG OUTPUT
RANGE SETTING AND CALIBRATION
See Page 7
Set the Decimal
Point (dp)
Bargraph Display
Scale Lo Range
Setting (bLo)
Bargraph Display
Scale hi Range
Setting (bhi)
[X•XXX]
[XX•XX]
[XXX•X]
[XXXX•]
[XXXX]
DECIMAL POINT AND
BRIGHTNESS SELECTION
See Page 5
DIGITAL SPAN SELECTION
FOR BARGRAPH DISPLAY
See Page 5
Goes directly
to Zero setting
if Analog Output
is not installed
+
–
4.00
+
–
20.00
1 Dimmest
2 Dim
3 Bright
4 Brightest
SETPOINT SETTING AND
RELAY CONFIGURATION MODE
See Page 8
L, h or
–
L, h or
–
L, h or
–
L, h or
–
Relay Activation
& Relay Disable
PROGRAMMABLE
OFFSET AND
SCALE FACTOR
See Page 4
Offset
Scale
Factor
Delay-on-Make
[doM]
Delay-on-Break
[dob]
0 to 9999
seconds
0 to 9999
seconds
Set Setpoint 1
[SP1]
Delay-on-Make
[doM]
Delay-on-Break
[dob]
0 to 9999
seconds
Setpoint 2
[SP2]
0 to 9999
seconds
Pump
[PUM]
Hysteresis
[hYSt]
Hysteresis
[hYSt]
Hysteresis
[hYSt]
Hysteresis
[hYSt]
Setpoint 3
[SP3]
Setpoint 4
[SP4]
This branch will only
appear if the Programming
Lock is engaged
This branch will only appear if the
Programming Lock is engaged.
When Lock is engaged, values
can be viewed, but not changed.
Calibration
Mode
v
When power is applied, all segments of the bargraph and
digital display light up for 3 seconds. The version number of
the installed software is then displayed for 2 seconds, after
which, the operational display indicates the input signal.
15 Second Program Timeout
Except for ZERO and SPAN settings in the Two Point Digital Calibration
Mode and the Analog Output Range Setting and Calibration Mode (cLo and
chi), the meter has a 15 second program timeout. If no buttons are pressed
for 15 seconds in any of the other programming sequences, the meter will
exit the programming mode and return to the operational display. Any pro-
gram changes that were made prior to pressing the
P
button in the preced-
ing step will not be saved.