background image

5

4

Installation

•   Remove temperature gauge.
•   Remove insulating shell.
•   Slide clip to release bracket, then reposition.
•   Install the bracket to the wall using the mounting screws supplied 

in the pack (1).

 

 

Insert the unit from the front, seating the pins as shown in the 
figure.  
The components are fastened to the bracket automatically by the 
clip (2).

•   Establish  the  position  for  installing  an  expansion  tank  (separately 

purchased) at a distance allowed by the length of the hose (3).

•   Install the piping for the entire system and connect the solar unit. 

Secure the components and the pipes to the rear insulation. 
Tighten all the fittings.

•   The unit’s threaded fittings are tightened and tested in the assembly 

phase in the factory.  However, use a pressure test to check for

  leaks during commissioning.

•   Make the electrical connections of the system, as specified in the 

solar controller instruction manual. 

  

Apply the front part of the insulation.

Filling the system

•   Open  the  shut-off  valve  coupled  with  the  automatic  air  vent, 

installed at the highest point of the solar thermal system.

•   Open the shut-off and check valves, located where the temperature 

gauge(s) insert.

•   Fill by with a pump, using the valve (A) located at the lowest point 

of the system, until air no longer comes out of the air vents. If the 
solar thermal system requires the use of glycol-water solution top-
off the system using the same glycol-water mixture.

•   Close the air vent shut-off valve.
•   Close valve (A).

A

1

2

3

Summary of Contents for 279 series

Page 1: ...ntial controller optional is suitable for management and control of 10 pre configured solar thermal system arrangements installed in an optional insulation jacket that mounts to the top of the pump st...

Page 2: ...ply before carrying out any work Failure in following these instructions may result in injury of persons or damage to property 2 Product range Code 278751A Single line solar pump station with 3 speed...

Page 3: ...uge scale 32 to 320 F 0 160 C Connections 3 4 female straight thread Hose connection 3 4 M Fill drain connections with hose connection 9 16 OD 15 mm Pump model Solar 15 68 Body cast iron GG 15 20 Elec...

Page 4: ...with air vent and shut off valve with check valve 7 Supply temperature gauge 8 Return temperature gauge 9 Pre formed shell insulation 10 Shut off ball valve with check valve with temperature gauge ho...

Page 5: ...t s threaded fittings are tightened and tested in the assembly phase in the factory However use a pressure test to check for leaks during commissioning Make the electrical connections of the system as...

Page 6: ...ate recommendations when setting the flow rate After the first few operating hours the solar thermal system must be purged of excess air again both in the highest point and on the air separator if equ...

Page 7: ...always be installed in a vertical position A thermometric label on the back of the flow meter signals if the maximum permitted temperature 230 F 110 C has been exceeded white temperature not exceeded...

Page 8: ...ation diagrams Shut off valve Pump Air vent Expansion tank Temperature gauge Safety valve Automatic filling 2 Shut off valve Pump Air vent Expansion tank Temperature gauge Safety valve Automatic filli...

Reviews: