Solar pump stations

NA28237

278-279 series

Function 

Solar pump stations are used on the primary 
circuit of solar thermal water heating systems to 
control the temperature of the hot water storage. 
The pump inside the unit is activated by the signal 
from a differential temperature controller. The unit 
contains the functional and safety devices for 
optimum circuit control. They are available with 
both supply and return connection or with return 
connection only.
The iSolar

PLUS temperature differential controller 

(optional) is suitable for management and control 
of 10 pre-configured solar thermal system 
arrangements installed in an optional insulation 
jacket that mounts to the top of the pump station 
for a nice clean assembly and simplified wiring 
(code 278011).

1

CONTENTS

Function

Important
Product range

Technical specifications

Characteristic components

Installation
Filling the system

Flushing the system
Commissioning
Draining the system

1

2-3

4

5

6

Shut-off and check valves
Air separator
Flow meter
Correction for different density liquids
Complete closing and opening of the valve

7

Application diagrams

8

INSTALLATION AND COMMISSIONING MANUAL

© Copyright 2015 Caleffi

www.caleffi.com

Summary of Contents for 279 series

Page 1: ...ntial controller optional is suitable for management and control of 10 pre configured solar thermal system arrangements installed in an optional insulation jacket that mounts to the top of the pump st...

Page 2: ...ply before carrying out any work Failure in following these instructions may result in injury of persons or damage to property 2 Product range Code 278751A Single line solar pump station with 3 speed...

Page 3: ...uge scale 32 to 320 F 0 160 C Connections 3 4 female straight thread Hose connection 3 4 M Fill drain connections with hose connection 9 16 OD 15 mm Pump model Solar 15 68 Body cast iron GG 15 20 Elec...

Page 4: ...with air vent and shut off valve with check valve 7 Supply temperature gauge 8 Return temperature gauge 9 Pre formed shell insulation 10 Shut off ball valve with check valve with temperature gauge ho...

Page 5: ...t s threaded fittings are tightened and tested in the assembly phase in the factory However use a pressure test to check for leaks during commissioning Make the electrical connections of the system as...

Page 6: ...ate recommendations when setting the flow rate After the first few operating hours the solar thermal system must be purged of excess air again both in the highest point and on the air separator if equ...

Page 7: ...always be installed in a vertical position A thermometric label on the back of the flow meter signals if the maximum permitted temperature 230 F 110 C has been exceeded white temperature not exceeded...

Page 8: ...ation diagrams Shut off valve Pump Air vent Expansion tank Temperature gauge Safety valve Automatic filling 2 Shut off valve Pump Air vent Expansion tank Temperature gauge Safety valve Automatic filli...