3
Performance
Suitalbe fluids:
water, glycol solution
Max. percentage of glycol:
50%
Maximum working temperature:
air separator side supply: 320°F (160°C)
pump side return:
230°F (110°C)
Max. working pressure:
145 psi (10 bar)
Safety relief valve working temperature range: -20 to 320°F (-30–160°C)
Safety relief valve setting:
90 psi (6 bar)
Check valve min. opening pressure (
D
p):
1/4 psi (2 kPa)
Shut-off and check valves working temperature range:
-20 to 320°F (-30–160°C)
Flow meter working temperature range:
15 to 230°F (-10–110°C)
Flow rate adjustment range:
2 to 8 gpm
Flow rate indicator accuracy:
±10%
Pressure gauge scale:
0 to 145 psi (0–10 bar)
Temperature gauge scale:
32 to 320°F (0–160°C)
Connections:
3/4” female straight thread
Hose connection:
3/4” M
Fill/drain connections:
with hose connection 9/16" OD (15 mm)
Pump model Solar 15-68
Body:
cast iron GG 15/20
Electric supply:
115 V 60 Hz
Max. pressure:
150 psi (10 bar)
Max. liquid temperature:
230°F (110°C)
Min. liquid temperature:
36°F (2°C)
Max. current:
0.61 A
Max. power consumption:
70 W
Protection class:
IP 42
Flow range:
0 to 10 gpm (0 to 2.3 m³/hr)
Head range:
0 to 33 ft (0 to 10 m)
Pump model UP-100 Drainback
Body:
cast iron GG 15/20
Electric supply:
115 V 60 Hz
Max. pressure:
150 psi (10 bar)
Max. liquid temperature:
205°F (96°C)
Min. liquid temperature:
36°F (2°C)
Max. current:
1.1 A
Max. power consumption:
135 W
Agency approval:
cULus
Flow range:
0 to 8.4 gpm (0 to 1.9 m³/hr)
Head range:
0 to 36 ft (0 to 11.0 m)
NOTE: pump data per manufacturer technical specifications.