8
110 Volt Installation Information
Always Follow Applicable Local, State, Federal Codes and Guidelines.
1. Use only a dedicated electrical line with a 20-amp breaker.
2. Do not use an extension cord.
3. Always use a weatherproof/covered receptacle.
4. Never have your spa with in 10 feet to the receptacle.
5. Do not bury the power cord.
6. A damaged cord must be replaced before next usage.
7. All 110-volt spas must have a GFCI. This can either be a 20 Amp GFCI receptacle or a GFCI cord and plug kit (CKIT110).
8. GFCI plug should be tested prior to every use. To test the GFCI plug version, please follow these easy instructions:
Note: Spa should be already plugged in and operational.
1. Press the button marked “Test” on the GFCI. The GFCI will trip and the spa will stop operating
2. Press the button marked “Reset” on the GFCI. The GFCI will reset and the spa will turn back on in about 5 seconds.
3. The spa is now safe to use.
If the GFCI should turn off (trip) while the spa is in use, press the reset button. If the GFCI will not reset, unplug the
GFCI and call your local Showroom/Dealership for service. DO NOT USE SPA.
110 Volt / 20 Amp GFCI Plug