8
5.6
010 LCD 2T, 010 LCD 4T
010 LCD 2T and 010 LCD 4T connections
H2*
water temperature probe 10kΩ
H4*
cold water temperature probe 10kΩ (only for
010 LCD 4T)
AIR
air temperature probe 10kΩ
M1
DC inverter fan motor
S1
grill safety micro-switch
Y1
water solenoid valve (230V/ 50Hz 1A output
voltage)
Y2
cold water solenoid (010 LCD 4T only) or mobile
flap connection (010 LCD 2T only).
230V/ 50Hz 1A output voltage.
L-N
230V/50Hz electrical power supply
BO
boiler consent output (free contact max 1A)
CH
chiller consent output (free contact max 1A)
CP
presence input sensor (if closed, the fan coil unit
is placed in standby).
HRS
RS water probe (2kΩ) (010 LCD 2T only)
RS
RS version cabling (010 LCD 2T only)
*
If after switching the power on the board
detects the H2 probe, start-up occurs in normal
conditions with the minimum water temperature
when heating (30°C) and maximum when
cooling (20°C).
The board also has a function when there is no
probe, in such cases the fan stop minimum and
maximum thresholds are ignored.