Connect the RS485 line of the wall-mounted remote control
to one or more (up ot a maximum of 30) devices fitted with
electronics for remote control MB 010 2T or MB 010 4T
using a suitable two-core cable for serial connections RS485
keeping the power supply cables separate.
-
Chase out the wall in order to minimise the length of
the leads;
-
complete the line with the supplied 120 Ω heating
element;
-
do not make "star" connections;
-
The RS485 cable connection is polarised, respect the
"A" and "B" indications on every periphery connected
(for connecting, it is preferable to use a shielded two-
core cable with a minimum thickness of 0.35 mm
2
);
-
connect the + and - power terminals on the wall
mounted terminal block, 5V DC, to one of the boards
MB 010 2T or MB 010 4T, respecting polarity.
WALL LCD Connections