Aquavision Control
Monitoring Module
Register 30019
Sub Water meter 2 Total Low Word
Register 30020
Sub Water meter 2 Total High Word
Register 30021
Sub water meter 2 Current flow Low word
Register 30022
Sub water meter 2 Current flow High word
Register 30025
Sub Water meter 3 Total Low Word
Register 30026
Sub Water meter 3 Total High Word
Register 30027
Sub water meter 3 Current flow Low word
Register 30028
Sub water meter 3 Current flow High word
Register 30031
Actual Temperature in ° C *10
Register 30032
Actual Pressure in ° Bar *10
Register 30033
Valve status Sub water meter 1
1 = Valve closed / 0= Valve
open
Register 30034
Valve status Sub water meter 2
1 = Valve closed / 0= Valve
open
Register 30035
Valve status Sub water meter 3
1 = Valve closed / 0= Valve
open
Register 30036
Status External command for Unlimited mode
1 = Input closed / 0 = Input
open
Register 30037
Status External leak input
1 = Input closed / 0 = Input
open
Register 30038
Status External Intrusion alarm input
1 = Input closed / 0 = Input
open
Register 30039
Time left in hours until Unlimited mode ends
Value in hours (0 - 24)
Register 30040
General Status AquaControl
1 = Alarm / 0 = System
normal
Register 30041
Alarm Sub water meter 1
1 = Sub water meter 1 alarm /
0 = System normal
Register 30042
Alarm Sub water meter 2
1 = Sub water meter 2 alarm /
0 = System normal
Register 30043
Alarm Sub water meter 3
1 = Sub water meter 3 alarm /
0 = System normal
Register 30044
Alarm between Street water meter and official water meter
distribution company
1 = Alarm / 0 = System
normal
Register 30045
Alarm Temperature Sensor Out of range
1 = Sensor alarm/0 = Sensor
normal
Register 30046
Alarm Pressure Sensor Out of range
1 = Sensor alarm/0 = Sensor
normal
Register 40001
Low temperature limit in ° C * 10
Register 40002
High temperature limit in ° C * 10
Register 40003
Low pressure limit in ° C * 10
Register 40004
High pressure limit in ° C * 10
Register 40005
Start Unlimited mode for 24 hours
To find out the total value of water consumption in a circuit, do the following calculation:
Register value (low word) + register value (high word)*65.535)