13
ZEFIRO
3
- ZEN AIRTIGHT
LEGEND
Fig. 15
3
55 cm
4
6,2 cm
5
17,7 cm
6
6,1 cm
7
49,4 cm
8
25,8 cm
9
14,5 cm
10
Exhaust fumes d.8 cm
11
Hole combustion air inlet d.6 cm
12
Hot air outlet 18x3 cm
13
Ducting outlet d.8 cm (optional)
14
37,7 cm
15
27,2 cm
16
7,5 cm
17
54÷72 cm
5.3
GENERAL INSTALLATION
Fig. 16 - General installation
LEGEND
Fig. 16
1
Fireplace insert
2
Minimum lateral distance = 240 mm
3
Minimum rear distance = 190 mm
4
Minimum front distance = 1000 mm
5
Minimum thickness of insulating material = 40 mm
• Please check that the floor has an adequate load capacity. If the existing one does not satisfy this requirement, appropriate
measure should be provided (for example a plate for distributing the load).
• It is obligatory to install the stove away from walls and/or pieces of furniture, with a minimum air flow of 240 mm on the sides
and 190 mm on the back, to enable an eficient appliance cooling and a good distribution of heat in the room (see
Fig. 16
).
• For safety fire regulations the distances from flammable or sensible to heat objects (sofas, pieces of furniture, wooden cove-
ring, etc...) must be respected, has described in
Fig. 16
.
The probable insulating material to use must have the following technical features:
DESCRIPTION
VALUE
Material thickness
40 mm