Fig. 32 - Display: AL 8
11.18 ALARM ALERTS
Whenever an operating condition other than that designed for the regular operation of the boiler occurs, there is an alarm condition.
The control panel gives information on the reason of the alarm in progress.
ALARM
CAUSE
SOLUTION
INTERVENTION
AL 1 - BLACK
OUT
Power cut during ignition
phase.
Clean the burning pot and switch the stove on again.
AL 2 - EXHAUST
PROBE
Disconnected fume tem-
perature probe
Have the stove checked.
Faulty fume temperature
probe
Replace the fume probe.
AL 3 - HOT
EXHAUST
Faulty fume probe
Replace the fume probe.
Faulty mother board
Replace the electronic board.
The exchanger fan does
not work
Replace the ambient fan.
Too high pellet drop value Adjust the pellet loading.
AL 4 - FAN
FAILURE
Faulty protection fuse of
the fume fan
Replace the fuse (1,25A).
Faulty fume fan
The pellets can burn also thanks to the chimney flue
depression and without the aid of the fume fan. Have the
fume fan replaced immediately. It can be noxious to health
to let the stove running without fume fan.