Page 13
509 Sharptown Road P.O. Box 345 Bridgeport, NJ 08014
Email: [email protected] Fax: 856-467-5511
Internet: http://caddycorp.com Phone: 856-467-4222
Ventilator Water Wash
(optional feature)
Operating and Installation
1.
Install piping (by others) and vacuum breaker from raceway to ventilator spray nozzles.
2.
Vacuum breaker must be installed at least six inches above ventilator spray nozzles.
3.
Turn hood wash system on. System should now be operating.
4.
Adjust pressure regulator to thirty pounds of pressure by following these steps:
a.
Loosen pressure regulator locknut.
b.
Turn regulator key until pressure gauge reads thirty pounds.
c.
Tighten pressure regulator locknut.