26
Make sure the piston is at Top Dead Center (TDC)
•
of its compression stroke (both valves closed). To
get the piston at TDC, remove the intake screen at
the front of the engine to gain access to the flywheel
nut. Use a large socket and socket wrench to rotate
the nut and hence the engine in a clockwise direc-
tion. While watching the piston through the spark
plug hole. The piston should move up and down.
The piston is at TDC when it is at its highest point
of travel.
To adjust valve clearance (if necessary), (Figure
4.9):
Make sure the engine is at 60° to 80° F.
•
Make sure that the spark plug wire is removed
•
from the spark plug and out of the way.
Remove the four screws attaching the valve cover.
•
Loosen the rocker jam nut. Use an 10mm allen
•
wrench to turn the pivot ball stud while checking
clearance between the rocker arm and the valve
stem with a feeler gauge. Correct clearance is
0.002-0.004 inch (0.05-0.1 mm).
Figure 4.9 - Valve Clearance Adjustment
Jam Nut
Pivot Ball
S
tud
Rocker
Arm
Valve
S
tem
NOTE:
Hold the rocker arm jam nut in place as the pivot
ball stud is turned.
When valve clearance is correct, hold the pivot ball
stud in place with the allen wrench and tighten the
rocker arm jam nut. Tighten the jam nut to 174 in/
lbs. torque. After tightening the jam nut, recheck
valve clearance to make sure it did not change.
Install new valve cover gasket.
•
Re-attach the valve cover.
•
NOTE:
Start all four screws before tightening or it will not
be possible to get all the screws in place. Make
sure the valve cover gasket is in place.
Install spark plugs.
•
Re-attach the spark plug wire to the spark plug.
•
On the GT-530 and GT-990/999, repeat the process
•
for the other cylinder.
4.8 COOLING
SYSTEM
Air inlet and outlet openings in the generator com-
partment must be open and unobstructed for con-
tinued proper operation. This includes such obstruc-
tions as high grass, weeds, brush, leaves and snow.
Without sufficient cooling and ventilating air flow, the
engine/generator quickly overheats, which causes it
to quickly shut down. (See Figure 4.10 for vent loca-
tions.)
Make sure the doors and roof are in place dur-
ing operation as running the generator with them
removed can effect cooling air movement.
Figure 4.10 – Cooling Vent Locations
The exhaust from this product gets extremely
hot and remains hot after shutdown. High grass,
weeds, brush, leaves, etc. must remain clear of
the exhaust. Such materials may ignite and burn
from the heat of the exhaust system.
The maximum ambient temperature for the gen-
erator is 25° C (77° F).
4.9 ATTENTION AFTER SUBMERSION
If the generator has been submerged in water, it
must
not
be started and operated. Following any submer-
sion in water, have a Dealer thoroughly clean, dry
and inspect the generator. If the structure (ex. home)
has been flooded, it should be inspected by a certi-
fied electrician to ensure there won't be any electrical
problems during generator operation or when utility
is returned.
Section 4 — Maintenance
Air-cooled Generators
Summary of Contents for 8kW
Page 1: ...Study Guide S e r v i c e T r a i n i n g Air Cooled Training...
Page 2: ......
Page 36: ...32 32 Section 7 Notes Air cooled Generators...
Page 37: ...33 Section 8 Installation Diagrams Air cooled Generators Circuit Breakers Drawing No 0G8573 A...
Page 38: ...34 Section 8 Installation Diagrams Air cooled Generators Generator Drawing No 0G8280 D...
Page 39: ...35 Section 8 Installation Diagrams Air cooled Generators Generator Drawing No 0G8280 D...
Page 42: ...Part No 0G8334 Revision D 09 16 08 Printed in U S A Catalog No OMASPCA S 01...
Page 58: ...14 Section 5 Electrical Data RTSS Type Transfer Switch Wiring Diagram Drawing No 0G7817 B...
Page 59: ...15 Section 5 Electrical Data RTSS Type Transfer Switch Wiring Diagram Drawing No 0G7817 B...
Page 64: ...20 Section 7 Notes...
Page 65: ...21 Section 7 Notes...
Page 66: ...Part No 0G8637 Revision D 08 27 08 Catalog No KGALT 1SI Printed in U S A...
Page 68: ......
Page 76: ...8 Residential Transfer Switch Installation Guide Installation Drawing 0H0258 A...
Page 77: ...9 Residential Transfer Switch Installation Guide Installation Drawing 0H0258 A...
Page 78: ...Residential Transfer Switch Installation Guide Installation Drawing 0G8573 A 10 10...
Page 79: ...11 Residential Transfer Switch Installation Guide Electrical Schematic Drawing 0G7959 A...
Page 80: ...12 Residential Transfer Switch Installation Guide Wiring Diagram Drawing 0G7958 A...
Page 81: ...13 Residential Transfer Switch Installation Guide Wiring Diagram Drawing 0G7958 A...
Page 82: ...14 Residential Transfer Switch Installation Guide Load Center Exploded View Drawing 0G8786 C...
Page 84: ...16 Residential Transfer Switch Installation Guide Notes...
Page 85: ...17 Residential Transfer Switch Installation Guide Notes...
Page 86: ...Part No 0G8571 Revision D 07 31 08 Catalog No KGATX100 1SI Printed in U S A...
Page 91: ...5 REFERENCE Items supplied in the EZ Transfer operator kit...
Page 92: ...6...
Page 93: ...7...
Page 95: ...Air cooled Generator Battery Charger Installation Guidelines...
Page 113: ...17 Section 6 Notes Battery Charger Installation Guidelines...
Page 114: ...Part No 0G7956 Revision B 11 14 08 Printed in U S A...
Page 115: ......