manualshive.com logo in svg
background image

Model NG-1 1150, NG-1 1500, NG-1 2000,  

and NG-1 3000 Stand-Alone Nitrogen Generator

Page 1 of 8 

JUNE 2020 

TFP1253

Worldwide 

Contacts

www.tyco-fire.com

IMPORTANT

Refer to Technical Data Sheet 

TFP2300 for warnings pertaining to 

regulatory and health information.

General 

Description

The TYCO NG-1 1150, NG-1 1500, NG-1 

2000, and NG-1 3000 Stand-Alone 

Nitrogen Generators are designed to 

facilitate the Dry Pipe Nitrogen Inerting 

(DPNI) process for controlling oxygen 

corrosion in dry and preaction fire 

sprinkler systems, and provide super-

visory maintenance gas. Designed 

for “plug and play” performance in a 

typical dry or preaction fire sprinkler 

system, the nitrogen generator utilizes 

membrane separation technology that 

produces 98%+ nitrogen on demand 

without the need for nitrogen storage.
The Nitrogen Generator is an on-site 

nitrogen generation system that 

is designed to be installed in-line 

between the compressed air supply 

and the sprinkler system riser(s). The 

system provides DPNI for single or mul-

tiple zones depending on:
•  the number of systems,

•  the volume of the largest system

•  the cumulative volume of all systems 

being supplied

The generator includes an external 

bypass valve for maintenance or for 

“fast fill” needs to meet the NATIONAL 

FIRE PROTECTION AGENCY (NFPA) 13 

30-minute fill requirement for dry pipe 

and preaction fire protection systems.
The Nitrogen Generator is designed 

to nitrogen inert all of the zones being 

served within 14 days. Thereafter, it 

will continue to automatically provide 

supervisory nitrogen gas sufficient for 

pressure maintenance of the fire sprin-

kler system(s).
The Nitrogen Generator facilitates the 

patented “fill and purge” breathing 

process in the fire sprinkler system 

when paired with an oxygen removal 

vent installed on the sprinkler riser such 

as the TYCO Manual Air Vent (TAV-D) 

or the TYCO Dry SMART Vent (TSV-D). 

Refer to TFP1262 for more information 

on TYCO Dry Air Vent (TAV-D), and to 

TFP1263 for more information on TYCO 

SMART Air Vent (TSV-D).

System Assembly

The TYCO Nitrogen Generator unit 

includes the following components:
•  Steel enclosure cabinet with mem-

brane type nitrogen generator (no 

nitrogen gas storage) and manual 

bypass

•  Power supply:

120 VAC/Single phase/60Hz  

(230 VAC/Single phase/50Hz)

•  Single point nitrogen/air discharge – 

1/2 in. NPT

•  Hour Run Meter
•  Cycle Counter

System Status

The TYCO Nitrogen Generator includes 

the following system status indicators:
•  Bypass Mode Alarm Indicator - 

Nitrogen generator is in the By-Pass 

mode (flashing indicator). See Fig-

ure 4.

•  Leak Monitoring Alarm - Nitrogen 

generator is running excessively 

(audible signal).

System Input/Output 

Signals

The TYCO Nitrogen Generator includes 

the following monitoring outputs:

Digital Outputs

•  Power On/Off
•  Bypass Mode Alarm 
•  Nitrogen Generator Running
•  Leak Monitoring

Analog Outputs

•  Nitrogen Supply Line Pressure

Support Equipment

The Nitrogen Generator is designed to 

be used in conjunction with the TYCO 

AMD-1 Air Maintenance Device, the 

TYCO Handheld Gas Analyzer (THGA), 

and the Riser-mounted TYCO Dry Air 

Vent (TAV-D), or TYCO Dry SMART 

Vent (TSV-D), as part of the com-

plete Dry Pipe Nitrogen Inerting (DPNI) 

system. Refer to TFP1267 for more 

information on the TYCO Handheld 

Gas Analyzer.
The TYCO Nitrogen Generator can 

be used with the following optional 

equipment:
•  TYCO Model TSGA SMART Gas 

Analyzer - one for each nitrogen 

generator is recommended. Refer to 

TFP1270 Model TSGA SMART Gas 

Analyzer for more information.

•  TYCO Model TILD In-Line Corro-

sion Detector - monitoring at least 

one for each sprinkler system is rec-

ommended. Refer to Technical Data 

Sheet TFP1261 TYCO Model TILD 

In-Line Corrosion Detector for more 

information.

TYCO NG1 

Compressors

The TYCO NG1 Compressors are 

paired with the TYCO NG-1 1150, 

NG-1 1500, NG-1 2000, and NG-1 

3000 Nitrogen Generator in facilitating 

the Dry Pipe Nitrogen Inerting (DPNI) 

process in dry and preaction fire sprin-

kler systems as well as Wet Pipe Nitro-

gen Inerting (WPNI) process in wet pipe 

sprinkler systems. The air compressors 

Содержание tyco NG-1 1150

Страница 1: ...on on TYCO Dry Air Vent TAV D and to TFP1263 for more information on TYCO SMART Air Vent TSV D System Assembly The TYCO Nitrogen Generator unit includes the following components Steel enclosure cabinet with mem brane type nitrogen generator no nitrogen gas storage and manual bypass Power supply 120 VAC Single phase 60Hz 230 VAC Single phase 50Hz Single point nitrogen air discharge 1 2 in NPT Hour ...

Страница 2: ...4605 1150 4353 2300 8706 NG 1 1500 24 3 688 11000 41640 1440 5451 2880 10902 NG 1 2000 24 688 18500 70030 2025 7666 4050 15331 NG 1 3000 35 992 22500 85172 2900 10978 5800 21955 Notes a Capacity based on NFPA 13 30 minute fill requirement of largest single system Model Number Cabinet Without Bypass Cabinet With Bypass Weight Lbs kg Width Inches mm Height Inches mm Depth Inches mm Width Inches mm H...

Страница 3: ... N2 Purity at Discharge 98 or greater maximum of 2 0 oxygen N2 Pressure at Discharge Minimum of 15 psig 1 bar Max of feed air pressure minus 15 psig 1 bar N2 Water Dew Point Typically less than 70 F 57 C Note When connecting a TYCO Stand Alone Nitrogen Generator to an existing dry pipe preaction fire sprinkler system the existing fire sprinkler system s must be limited to a maximum leak rate of le...

Страница 4: ... The nitrogen air discharge plumb ing from the nitrogen generator is to be connected directly to the sprinkler system valve trim using a minimum of 1 2 in to 1 in black steel galva nized steel or copper piping The size of the nitrogen air supply line is to be based on the length of pipe between the nitrogen generator and the fire sprinkler systems along with the total volume of the fire sprinkler ...

Страница 5: ...GENERATOR RUNNING OUTPUT BYPASS MODE ALARM OUTPUT LEAK MONITORING OUTPUT POWER ON OFF OUTPUT NITROGEN SUPPLY LINE PRESSURE OUTPUT L1 N G PRESSURE SWITCH INCOMING POWER FUSE BOX BUILDING MANAGEMENT SYSTEM MONITORING POINTS POWER SUPPLY POWER DISTRIBUTION L1 G N N N G FIGURE 2A MODEL NG 1 1150 NG 1 1500 NG 1 2000 AND NG 1 3000 STAND ALONE NITROGEN GENERATOR AMERICAS SYSTEM SIGNAL MONITOR AND POWER S...

Страница 6: ... drain connection be plumbed to a floor drain or building exterior When plumbing to a drain is not feasible an evaporative collection chamber can be used Note Ensure that the receiver tank auto drain is connected to an un switched power source 120 VAC for Americas 230 VAC for EMEA and APAC Note The Low Oil Level Sensor on the air compressor automatically shuts down air compressor until the proper ...

Страница 7: ...rnal inlet piping by slowly opening the Depressurization Ball Valve in the cabinet to the left of the filter housing Step 4 Remove the filter housing by pulling down on the blue housing lock and turning the filter housing count er clock wise Step 5 Once the filter housing has been removed the filter cartridge inside is removed by first unscrewing the black retaining disc at the base of the cartrid...

Страница 8: ...he Bypass Ball Valve Step 13 Open the Inlet and Outlet Ball Valves Compressors Maintenance of the Compressor For compressor maintenance please refer to the manufacturer s recom mended maintenance plan in the owner s manual for the compressor Limited Warranty For warranty terms and conditions visit www tyco fire com Ordering Procedure TYCO will supply a list of required part numbers to order throug...

Отзывы: