background image

 9 

 

Advanced programming 

Parameter Name   Default Value  

Range / Options   Description  

UHS5  UNLCDHS 

Channel 1 –Switching Channel( PRM & AD only)

 

Lux on level 

(Switch level on) 

1 to 9 

For a higher resolution 
a scale of 101-199 is 
available 

Sets a minimum light level below which the PIR sensor is enabled, allowing lights 
to be turned on by movement. 

Note: the Lux Level Off value must always be greater than the Lux Level On value. 

   

Lux off level 

(Switch level off) 

1 to 9 

For a higher resolution 
a scale of 101-199 is 
available 

Sets a maximum light level above which the PIR sensor is disabled, preventing 
lights from being turned on by movement. 

   

Channel 2 -Dimming Channel (DD & AD only)

 

Lux on level 

(Switch level on) 

1 to 9 

For a higher resolution 
a scale of 101-199 is 
available 

Sets a minimum light level below which the PIR sensor is enabled, allowing lights 
to be turned on by movement. 

Note: the Lux Level Off value must always be greater than the Lux Level On value. 

   

Lux off level 

(Switch level off) 

1 to 9 

For a higher resolution 
a scale of 101-199 is 
available 

Sets a maximum light level above which the PIR sensor is disabled, preventing 
lights from being turned on by movement. 

   

Light Level 

(maintained illuminance) 

600 

1 to 998 (999 
disabled) 

Sets a target light level to be maintained by the lighting system.  

   

Load Type 

(DD only)

 

DALI 

DSI 
DALI 
 
DALI On 

Sets the ballast control protocol to DSI. 
Sets the ballast control protocol to DALI. 
 
 
DALI On provides a permanent voltage to DALI ballasts when DALI has not been 
implemented correctly in the ballast. Maximum number of ballasts is 4 unless the 
relay is disabled then it is 10. 

 
 

 

 
 

 

Max Value 

100% 

0 to 100% 

Maximum dimming output level. 

   

Min Value 

0% 

0 to 100% 

Minimum dimming output level. 

   

Memorise 

Yes or No 

If this is set to Yes, the last manual lux level set will be memorised and used as the 
new switch on level. 

   

On value 

99 

0 to 99 

Dimming output level when switched on (0-99). 

   

Off value 

0 to 99 

Dimming output level when switched off (0-99). If a non-zero off value is set, then 
the output will toggle between this value and completely off depending on the 
switch level on and off values. For example, if it is light outside, the fittings will be 
off if there is no occupancy. If it is dark outside, they will adopt the preset off value. 
This feature is only enabled if ‘Min value’ is set to 99. 

   

Burn-in 

0 (disabled) or 
1 to 999 hours 

Determines how long the output will be at 100% so that lamps ‘burn-in’. The ’burn-
in’ time is not affected by power supply interruptions.  

   

Fade value 

10 

0 to 99 

After occupancy ceases, this dimming output level is loaded for the fade time 
(adjustable between 0 and 99).  

   

Fade mins 

0 to 99 

This is the time period (adjustable between 0 and 99 minutes) that the luminaire 
will be held at the fade value before turning off. A value of 0 disables the fade 
function. 

   

Speed On 

40 

Measured in 0.1 
sec intervals. 

Determines the dimming response speed after the setup time has finished. 

   

Speed Set 

Measured in 0.1 
sec intervals. 

Determines the dimming response speed during the set up time. Measured in 0.1 
sec intervals.  If set to 0 will disable dimming for “Set seconds” below, used if 
fittings are required to warm up before dimming. 

   

Set Seconds 

120 

1 to 999 seconds 

Determines how long the dimming response set-up period lasts on power-up or on 
setting change. This enables the desired lux level to be achieved rapidly when the 
lights come on, or during setup. 

   

Summary of Contents for EBMINT

Page 1: ...al control using an infrared handset It is specifically designed for mounting onto a lamp or louvre using the louvre fitting bracket Three models are available premium direct dim and analogue dim all...

Page 2: ...ection diagram Range Walk towards Walk across Height Range Diameter 7m 10m 2 8m 5m Height Range Diameter 7m 16m 2 8m 9m Note illustration shows an average of the walk across and walk towards figures b...

Page 3: ...er s datasheet for details As the EBMINT DD AD are able to dim the lamps using DALI DSI or 1 10V the products provide a facility to disable this for a given period of time Operation By setting the Bur...

Page 4: ...ube The cable must not touch the any part of the lamp 1 2 3 4 1 2 3 4 1 2 Louvre fitting Compact reflector fitting 1 2 3 4 Select correct clip for lamp T5 or T8 Panel mounting using lugs Use the lugs...

Page 5: ...knockout or between gear tray and housing of luminaire Connect the Neutral Disconnect the Live to the ballast Using the supplied terminal block connect the Live switched output Black from detector to...

Page 6: ...ive supply to the circuit is good Check that the load is functioning by bypassing the sensor e g link L and L Out HINT The Walk Test LED function can be used to check that the unit is detecting moveme...

Page 7: ...g Note the Lux Off Level value must always be greater than the Lux On Level value Load Type DD only DALI 2 DALI 7 DSI 2 DALI on Sets the ballast control protocol to be used by the output channel Sensi...

Page 8: ...e On Delay to allows the first channel to switch on after the second channel A typical application for this would be where a detector is controlling lighting and air conditioning in an area When the o...

Page 9: ...then it is 10 Max Value 100 0 to 100 Maximum dimming output level Min Value 0 0 to 100 Minimum dimming output level Memorise N Yes or No If this is set to Yes the last manual lux level set will be me...

Page 10: ...AD On 344mW Off 268mW Cable specification 1m silicon insulation and sheath PRM 3 x 0 75mm2 AD DD 3 x 0 75mm2 2 x 0 50mm2 Temperature 10 C to 50 C Humidity 5 to 95 non condensing Material Flame retarda...