 3 

 

Detection mode 

 

Presence

 When movement is detected the load will automatically turn on. When the area is no longer occupied the 

load will automatically switch off after an adjustable time period.  
Sensitivity to movement of the PIR sensor can be adjusted using the Sensitivity parameter. 

HINT: To assist in setting the Sensitivity, turn on the Walk Test LED which will flash red when movement is detected. 

Switch Level On/Off 

Occupancy detection can be made dependant on the ambient light level using the Lux On Level and Lux Off Level 
parameters. 

 
 
 
 
 
 
 
 
 
 
 
 
 

Maintained Illuminance (daylight harvesting) - DD and AD variants only 

The detector measures the overall light level in the detection area and calculates the correct output for the luminaires, to 
achieve a preset lux level (maintained illuminance or daylight harvesting). 

Burn-in - DD and AD variants only 

 

Overview 

It is a requirement of many fluorescent lamp manufacturers to have the lamps on at maximum output for a period of 

time to guarantee lamp life (refer to the manufacturer’s datasheet for details). As the EBMINT-DD & AD are able to 
dim the lamps using DALI/DSI or 1-10V, the products provide a facility to disable this for a given period of time. 

 

Operation 

By setting the “Burn in” parameter, you can select a time during which the lamps are not allowed to deviate from 

maximum output. The unit counts the time, and even remembers how long has elapsed in the event of a power 
failure. To cancel the burn in function, simply select a time of 0. Note that when the lamps are changed, the burn in 
time should be set again. 

Sensor functionality 

Burn-in - DD and AD variants only 

The product is designed to be mounted directly to the outside of a luminaire. The detector should be sited so that the 
occupants of the room fall inside the detection pattern (shown opposite), at a recommended ceiling height of 2.8m. Note 
that the lower the sensor is installed the smaller the detection range will be, subject to the parameters shown on the 
detection diagram. 

 

For optimum operation of the lux sensor, the lens must shielded as much as possible from the light source. 

 

Avoid direct sunlight entering the sensor.  

 

Do not site within 1m of forced air heating or ventilation.   

 

Do not fix to a vibrating surface. 

Installation 

Summary of Contents for EBMINT

Page 1: ...al control using an infrared handset It is specifically designed for mounting onto a lamp or louvre using the louvre fitting bracket Three models are available premium direct dim and analogue dim all...

Page 2: ...ection diagram Range Walk towards Walk across Height Range Diameter 7m 10m 2 8m 5m Height Range Diameter 7m 16m 2 8m 9m Note illustration shows an average of the walk across and walk towards figures b...

Page 3: ...er s datasheet for details As the EBMINT DD AD are able to dim the lamps using DALI DSI or 1 10V the products provide a facility to disable this for a given period of time Operation By setting the Bur...

Page 4: ...ube The cable must not touch the any part of the lamp 1 2 3 4 1 2 3 4 1 2 Louvre fitting Compact reflector fitting 1 2 3 4 Select correct clip for lamp T5 or T8 Panel mounting using lugs Use the lugs...

Page 5: ...knockout or between gear tray and housing of luminaire Connect the Neutral Disconnect the Live to the ballast Using the supplied terminal block connect the Live switched output Black from detector to...

Page 6: ...ive supply to the circuit is good Check that the load is functioning by bypassing the sensor e g link L and L Out HINT The Walk Test LED function can be used to check that the unit is detecting moveme...

Page 7: ...g Note the Lux Off Level value must always be greater than the Lux On Level value Load Type DD only DALI 2 DALI 7 DSI 2 DALI on Sets the ballast control protocol to be used by the output channel Sensi...

Page 8: ...e On Delay to allows the first channel to switch on after the second channel A typical application for this would be where a detector is controlling lighting and air conditioning in an area When the o...

Page 9: ...then it is 10 Max Value 100 0 to 100 Maximum dimming output level Min Value 0 0 to 100 Minimum dimming output level Memorise N Yes or No If this is set to Yes the last manual lux level set will be me...

Page 10: ...AD On 344mW Off 268mW Cable specification 1m silicon insulation and sheath PRM 3 x 0 75mm2 AD DD 3 x 0 75mm2 2 x 0 50mm2 Temperature 10 C to 50 C Humidity 5 to 95 non condensing Material Flame retarda...