Advanced programming 

Parameter Name  

Default Value   Range / Options   Description  

UHS5  UNLCDHS 

Detector Parameters

 

Walk Test LED 

Off 

On or Off 

When set to On this causes a red LED to flash on the sensor when it detects 

movement. Use this feature to check for adequate sensitivity levels. 

   

Time Out 

(Time adjustment) 

20 minutes 

0-99 minutes 

Once the detector is turned on, this value sets how long the lights will stay on once 

movement has ceased. Select 0 for 10 second delay – use for commissioning only.  

   

Manual Time Out 

10 minutes 

0-99 minutes 

When a manual operation occurs, either via the switch input or the infrared, it 

invokes the timeout period. 

Example 1: a detector in presence mode has a detector timeout of 15 minutes and 

a manual timeout of 3 minutes. When the user leaves the room they press the off 

button. The sensor will revert to automatic after 3 minutes, and then walking back 

in the room will turn the lights on. 

Example 2: using the settings above, the user turns the lights off (say for a 

presentation) but stays in the room. Every time a movement is detected, the 

manual timeout period is re-triggered, but when it doesn’t pick up for the short 

timeout period, the sensor will timeout and revert to automatic. This means the 

lights may turn on inadvertently during the presentation, if the occupants are still 

for the manual timeout period, so adjust the timing carefully. 

   

Sensitivity On 

1 (min) to 9 (max) 

Sensitivity level for detecting movement when the detector is already on.  

*UHS5 

sets Sensitivity On and Off to the same value. 

*

   

Sensitivity Off 

1 (min) to 9 (max) 

Sensitivity level for detecting movement when the detector is off.  

*UHS5 sets 

Sensitivity On and Off to the same value.

 

*

   

Lux time 

0 (disabled) 
1-99 minutes 

If the detector measures the lux level and decides that the output needs switching 
on or off as a consequence, the lux time must elapse first. If at any time during the 
timed delay the lux change reverses then the process is cancelled. 

   

Power Up State 

On 

On or Off 

Select No for a 30 second delay on start up. If Yes is selected,   there will be no 

delay on start up and the detector will always  power up detecting. 

   

Disable Detector 

Y or N 

Disables detection, leaving the relay output permanently off with the dimming 

output operational. This mode is used when the unit is for maintained illuminance 

only.  

   

On Delay 

0 minutes 

0-99 minutes 

The On Delay to allows the first channel to switch on after the second channel. A 

typical application for this would be where a detector is controlling lighting and air 

conditioning in an area. When the occupant is detected, the lighting will be turned 

on immediately, whereas the air conditioning may be turned on after 15 minutes. If 

the area is vacated and the detector times out before the delay, then the air 

conditioning would never go on. The delay can be set only for channel 1 using the 

on delay parameter. 

   

Inhibit 

4 seconds 

1 to 999 seconds 

When the detector turns off, a delay is instigated to prevent retriggering. In certain 

circumstances this delay may not be enough. This parameter allows the delay to 

be changed. 

   

Factory default 

Restores factory default settings 

   

User Modes

 

Raise 

(DD & AD 

only)

 

Increase light level. Reverts when occupancy cycle complete. 

   

Lower 

(DD & AD 

only)

 

Decrease light level. Reverts when occupancy cycle complete. 

   

Scene up 

Steps up between 6 pre-defined scenes. 

   

Scene down 

Steps down between 6 pre-defined scenes. 

   

Scene # 

Select the individual scene, between 0 and 6. 

(1 = min. output; 2 = 10%;   3 = 25%; 4 = 50%; 5 = 75%; 6 = 100%) 

   

Override On 

If the lights are off, sending the IR command will turn them on immediately and 

revert to automatic operation using the manual timeout period. 

   

Override Off 

If the lights are on, sending the IR command will turn them off immediately. After 

the manual timeout period (described above), the sensor will revert to automatic. 

   

Cancel 

Cancels the on or off override, returning the detector to normal operation.  

   

The UNLCDHS has the ability to read back the settings stored in a device. 

To read back individual parameters 

 

Navigate to the parameter and press the ‘R’ (Read) button whilst pointing at the device. The handset will click 

when the parameter has been read back, the device will flash its LED, and the value will be shown against the 

parameter in the menu. 

To read back all of the parameters in a menu 

 

Press and hold the ‘R’ (Read) button for more than 1 second. 

 

The handset will click every time a parameter is received 

 

The device will show multiple flashes of its LED 

 

All of the values will be shown against the parameters in the menu. 

 

The individual parameters may be edited and then saved as a ‘Macro’. 

Notes 

 

If a parameter(s) has been missed because of a communication error, the missing value(s) is replaced by dashes. 

 

When reading back, the Channel 1 relay (where fitted) will temporarily be switched off, and will return to it’s 

normal state 2 seconds after the read back has been completed. 

Readback function 

(only with UNLCDHS handset )

 

Summary of Contents for EBMINT

Page 1: ...al control using an infrared handset It is specifically designed for mounting onto a lamp or louvre using the louvre fitting bracket Three models are available premium direct dim and analogue dim all...

Page 2: ...ection diagram Range Walk towards Walk across Height Range Diameter 7m 10m 2 8m 5m Height Range Diameter 7m 16m 2 8m 9m Note illustration shows an average of the walk across and walk towards figures b...

Page 3: ...er s datasheet for details As the EBMINT DD AD are able to dim the lamps using DALI DSI or 1 10V the products provide a facility to disable this for a given period of time Operation By setting the Bur...

Page 4: ...ube The cable must not touch the any part of the lamp 1 2 3 4 1 2 3 4 1 2 Louvre fitting Compact reflector fitting 1 2 3 4 Select correct clip for lamp T5 or T8 Panel mounting using lugs Use the lugs...

Page 5: ...knockout or between gear tray and housing of luminaire Connect the Neutral Disconnect the Live to the ballast Using the supplied terminal block connect the Live switched output Black from detector to...

Page 6: ...ive supply to the circuit is good Check that the load is functioning by bypassing the sensor e g link L and L Out HINT The Walk Test LED function can be used to check that the unit is detecting moveme...

Page 7: ...g Note the Lux Off Level value must always be greater than the Lux On Level value Load Type DD only DALI 2 DALI 7 DSI 2 DALI on Sets the ballast control protocol to be used by the output channel Sensi...

Page 8: ...e On Delay to allows the first channel to switch on after the second channel A typical application for this would be where a detector is controlling lighting and air conditioning in an area When the o...

Page 9: ...then it is 10 Max Value 100 0 to 100 Maximum dimming output level Min Value 0 0 to 100 Minimum dimming output level Memorise N Yes or No If this is set to Yes the last manual lux level set will be me...

Page 10: ...AD On 344mW Off 268mW Cable specification 1m silicon insulation and sheath PRM 3 x 0 75mm2 AD DD 3 x 0 75mm2 2 x 0 50mm2 Temperature 10 C to 50 C Humidity 5 to 95 non condensing Material Flame retarda...