GE SNPX Protocol – PLC Error Code Tables (cont’d)
(PLC generated error codes for the GE Fanuc 90-30, 90-70 and VersaMax SNPX protocol
continued on the next page.)
®
PLC Errors for GE SNPX Protocol (Minor-Major) (cont’d)
Panel Error Code
P499 Hex Value
Description
0x8D0A
Bad DOS Version. Must have DOS 2.0, or later, to support the SNP DOS Driver.
0x8E0A
PC Serial port configured for SNP Master driver is not open; no communication can take place.
0x8F0A
Out–of–Sequence SNP message. SNP message type received was not the type expected.
0x900A
Bad SNP BCC encountered. Transmission was aborted after maximum retries due to a bad Block Check
Code.
0x910A
Bad SNP communication. Transmission was aborted after maximum retries due to serial errors (that is,
parity, overrun, or framing errors).
0x920A
No SNP communication. Either communication has been lost or a communication session has not been
established.
0xC105
Invalid block state transition.
0xC205
The OEM key is NULL (inactive).
0xC305
Text length does not match traffic type.
0xC405
Verify with FA Card or EEPROM failed.
0xC505
No task–level Rack/Slot configuration to read or delete.
0xC605
Control Program (CP) tasks exist but requestor not logged into main CP.
0xC705
Passwords are set to inactive and cannot be enabled or disabled.
0xC805
Password(s) already enabled and can not be forced inactive.
0xC905
Login using non–zero buffer size required for block commands.
0xCA05
Device is write–protected.
0xCB05
A comm or write verify error occurred during save or restore.
0xCC05
Data stored on device has been corrupted and is no longer reliable.
0xCD05
Attempt was made to read a device but no data has been stored on it.
0xCE05
Specified device has insufficient memory to handle request.
0xCF05
Specified device is not available in the system (not present).
0xD005
One or more PLC modules configured have unsupported revision.
0xD105
Packet size or total program size does not match input.
0xD205
Invalid write mode parameter.
0xD305
User Program Module (UPM) read or write exceeded block end.
0xD405
Mismatch of configuration checksum.
0xD505
Invalid block name specified in datagram.
0xD605
Total datagram connection memory exceeded.
0xD705
Invalid datagram type specified.
0xD805
Point length not allowed.
0xD905
Transfer type invalid for this Memory Type selector.
0xDA05
Null pointer to data in Memory Type selector.
0xDB05
Invalid Memory Type selector in datagram.
0xDC05
Unable to find connection address.
0xDD05
Unable to locate given datagram connection ID.
0xDE05
Size of datagram connection invalid.
0xDF05
Invalid datagram connection address.
EA1-MG6-USER-M Hardware User Manual, 1st Ed. Rev C, 09/10
A
Appendix A: Panel & PLC Error Code Tables
A–19
Summary of Contents for EA-MG6-BZ2
Page 2: ......
Page 4: ......
Page 8: ......
Page 14: ......
Page 62: ......
Page 70: ......
Page 126: ......
Page 133: ...Notes 7 7 Chapter 7 Maintenance 7 EA1 MG6 USER M Hardware User Manual 1st Ed Rev C 09 10 ...
Page 134: ......
Page 148: ......
Page 178: ......
Page 188: ......
Page 189: ......