6–34
Chapter 6: PLC Communications
6
®
EA1-MG6-USER-M Hardware User Manual, 1st Ed. Rev C, 09/10
®
®
RS-422A/RS-485A Multi-Drop Wiring Diagram Examples
Note: We recommend Belden 8103 shielded cable or equivalent.
shield
7
RTS+
CTS–
CTS+
RTS–
RXD–
RXD+
TXD–
TXD+
GND
Direct
LOGIC
DL205 PLC
Direct
LOGIC
DL06 PLC
HD = High Density
10 9 6
13 11 14 12 15
15-pin
HD D-sub
(male)
8 = do not use
7 = Sig GND
6 = RXD–
5 = do not use
4 = do not use
3 = do not use
2 = do not use
1 = do not use
15 = CTS–
14 = CTS+
13 = RXD+
12 = RTS-
11 = RTS+
10 = TXD–
9 = TXD+
1
6
15
7
RTS+
CTS–
CTS+
RTS–
RXD–
RXD+
TXD–
TXD+
GND
10 9 6 13 11 14 12 15
TXD+
TXD
Signal GND
Signal GND
Typical RS-422 Multi-Drop Wiring Diagram
Port 2
Shielded Cable
Shielded Cable
To DL06 PLC port 2
Port 2
To D2-250-1 PLC port 2
RXD
RXD+
TXD+
TXD
RXD
RXD+
*
* Termination resistors required at both ends of the
network receive data signals to match the impedance
of the cable (between 100 and 500 ohms).
(Slave)