56
these failure types are the result of a casting defect the
warranty does not apply. Clearly it is in everyone’s best
interest to prevent this type of failure. The maintenance
of system integrity is the best method to achieve this.
I.
OXYGEN CORROSION:
Oxygen contamination of the boiler water will cause
corrosion of iron and steel boiler components, and can
lead to boiler failure. Burnham Commercial's standard
warranty does not cover problems caused by oxygen
contamination of boiler water or scale (lime) build-up
caused by frequent addition of water.
La contamination par l'oxygène de l'eau de la chaudière
entraînera la corrosion des composants de la chaudière
en fer et en acier et peut entraîner une panne de
la chaudière. La garantie standard de Burnham
Commercial ne couvre pas les problèmes causés par la
contamination par l'oxygène de l'eau de la chaudière ou
par l'accumulation de tartre (calcaire) causée par l'ajout
fréquent d'eau.
There are many possible causes of oxygen
contamination such as:
a. Addition of excessive make-up water as a
result of system leaks.
b. Absorption through open tanks and fittings.
c. Oxygen permeable materials in the
distribution system.
In order to ensure long product life, oxygen
sources should be eliminated. This can be
accomplished by taking the following measures:
a. Repairing system leaks to eliminate the need
for addition of make-up water.
b. Eliminating open tanks from the system.
c. Eliminating and/or repairing fittings which
allow oxygen absorption.
d. Use of non-permeable materials in the
distribution system.
e. Isolating the boiler from the system water by
installing a heat exchanger.
Minimum Water Quality Requirements
pH - 8.3 - 10.5
TDS - 3500 ppm
Total alkalinity ppm as CaCO
3
- 1200
Total copper ppm - .05
Oily matter ppm -1
total harness ppm -3
Chlorides - < 50 ppm
Summary of Contents for V1104H
Page 10: ...10 SECTION I GENERAL INFORMATION Figure 1 Dimensional Information...
Page 18: ...18 V11H SECTION ARRANGEMENT Figure 8...
Page 24: ...24 SECTION III INSTALLATION INSTRUCTIONS Figure 15 Bare Boiler Assembly...
Page 28: ...28 Figure 20 V11H Series Jacket Assembly Boiler Models V1104H Thru V1112H...
Page 29: ...29 Figure 21 V11H Series Jacket Assembly Boiler Models V1113H Thru V1123H...
Page 33: ...33 Figure 28 Minimum Piping Recommendations for V11H Series Tankless Heater Manifolds...
Page 39: ...39 Figure 32 V11H Series Minimum Piping Recommendation Primary Secondary Water...
Page 40: ...40 Figure 33 Minimum Piping Details Bypass With Blend Pump...
Page 44: ...44 0 Figure 37 Minimum Piping Requirements V11H Series Steam Boilers Gravity Return...
Page 49: ...49 Figure 42a DHW Generation with Tankless Coils Storage Tank and Destratification Pump...
Page 50: ...50 Figure 42b DHW Generation with Indirect Water Heater...
Page 69: ...69 Figure 45 V11H Series Jacket Assembly Boiler Models V1104H Thru V1112H...
Page 71: ...71 Figure 46 V11H Series Jacket Assembly Boiler Models V1113H Thru V1123H...
Page 73: ...73 Figure 47 Bare Boiler Assembly...
Page 75: ...75 Figure 47 Bare Boiler Assembly...
Page 78: ...78...
Page 79: ...79...
Page 80: ...80 Burnham Commercial P O Box 3939 Lancaster PA 17604 Revised November 1 2021...