
53
Ne pas faire fonctionner la chaudière avec une
pression supérieure à la pression de service
maximale autorisée indiquée sur l'étiquette de
classification de la chaudière.
NE PAS aspirer d'eau de la chaudière pendant
son utilisation. Lors de l'ajout d'eau pendant
que la chaudière est en marche, n'ouvrez pas
complètement la vanne d'alimentation mais ajoutez
de l'eau lentement.
C
.
SET CONTROLS with burner service switch turned
“OFF.”
1. PRESS RESET BUTTON on primary control and
release.
2. On STEAM BOILERS set cutout pressure (MAIN
scale) on L404 Pressuretrol for five (5) PSI and
differential pressure (DIFF scale) for two (2) PSI.
These pressures may be varied to suit individual
requirements of installation.
3. On STEAM BOILERS WITH TANKLESS
DOMESTIC WATER HEATERS, set boiler
water temperature dial on low limit operating
control at 190°F (max.). Set differential at 10°.
4. ON WATER BOILERS WITHOUT
TANKLESS HEATERS, set high limit dial on
L4006A at 210°F. This temperature may be varied
to suit requirements of installation.
5. ON WATER BOILERS WITH TANKLESS
HEATERS, set low limit operating control dial at
190°F and high limit dial 210°F. Operating control
must be a minimum of 20 below high limit setting.
Set differential at 25°.
D
.
ADJUST BURNER
according to the Burner Manual.
1. FLAME FAILURE
The V11H boiler controls operate the burner
automatically. If for unknown reasons the burner
ceases to fire and the reset button on the primary
control is tripped, the burner has experienced
ignition failure. Before pressing the reset button,
call your serviceman immediately.
Do not attempt to start the burner when excess oil or gas
has accumulated in the combustion chamber, when the
unit is full of vapor, or when the combustion chamber
is very hot.
N'essayez pas de démarrer le brûleur lorsqu'un excès
d'huile ou de gaz s'est accumulé dans la chambre de
combustion, lorsque l'unité est pleine de vapeur ou
lorsque la chambre de combustion est très chaude.
E.
TEST CONTROLS
Before installation the boiler is considered complete,
the operation of the boiler controls should be checked,
particularly the low water cutoff and the high limit control.
Avant que l'installation de la chaudière ne soit considérée
comme terminée, le fonctionnement des commandes de
la chaudière doit être vérifié, en particulier la coupure de
bas niveau d'eau et la commande de limite haute.
1. CHECK OPERATING CONTROL OPERATION.
Raise and lower operating control setting as required
to start and stop burner.
2. CHECK OPERATION OF HIGH LIMIT
CONTROL.
Jumper Operating Control Terminals. Allow burner
to operate until shutdown by limit. Installation is not
considered complete until this check has been made.
REMOVE JUMPER.
3. CHECK LOW WATER CUTOFF control with water
level at normal water line (see Figure 1). Raise
operating control setting to allow burner to operate.
Open boiler drain to allow water level to drop to
bottom of sight glass until burner operation is shut
down by low water cutoff.
Close boiler drain and refill to normal water line.
Burner should automatically restart during fill.
RESET OPERATING CONTROL.
Probe and float type low water cutoff devices require
annual inspection and maintenance.
Les dispositifs de coupure de bas niveau d'eau de
type sonde et flotteur nécessitent une inspection et un
entretien annuels.
Refer to Section V, Paragraph (C) for proper cleaning
instructions.
4. CHECK OPERATING CONTROL on boiler
equipped with tankless heaters. With burner off,
draw hot water until burner starts, then turn off hot
water and check burner shutdown.
F.
BOILER AND SYSTEM CLEANING - STEAM
BOILER
A qualified water treatment chemical specialist should be
consulted for recommendations regarding appropriate
chemical compounds and concentrations which are
compatible with local environmental regulations.
Summary of Contents for V1104H
Page 10: ...10 SECTION I GENERAL INFORMATION Figure 1 Dimensional Information...
Page 18: ...18 V11H SECTION ARRANGEMENT Figure 8...
Page 24: ...24 SECTION III INSTALLATION INSTRUCTIONS Figure 15 Bare Boiler Assembly...
Page 28: ...28 Figure 20 V11H Series Jacket Assembly Boiler Models V1104H Thru V1112H...
Page 29: ...29 Figure 21 V11H Series Jacket Assembly Boiler Models V1113H Thru V1123H...
Page 33: ...33 Figure 28 Minimum Piping Recommendations for V11H Series Tankless Heater Manifolds...
Page 39: ...39 Figure 32 V11H Series Minimum Piping Recommendation Primary Secondary Water...
Page 40: ...40 Figure 33 Minimum Piping Details Bypass With Blend Pump...
Page 44: ...44 0 Figure 37 Minimum Piping Requirements V11H Series Steam Boilers Gravity Return...
Page 49: ...49 Figure 42a DHW Generation with Tankless Coils Storage Tank and Destratification Pump...
Page 50: ...50 Figure 42b DHW Generation with Indirect Water Heater...
Page 69: ...69 Figure 45 V11H Series Jacket Assembly Boiler Models V1104H Thru V1112H...
Page 71: ...71 Figure 46 V11H Series Jacket Assembly Boiler Models V1113H Thru V1123H...
Page 73: ...73 Figure 47 Bare Boiler Assembly...
Page 75: ...75 Figure 47 Bare Boiler Assembly...
Page 78: ...78...
Page 79: ...79...
Page 80: ...80 Burnham Commercial P O Box 3939 Lancaster PA 17604 Revised November 1 2021...