61
TABLE 14.3: SOFT LOCKOUT CODES DISPLAYED
CODE
CONDITION
POSSIBLE CAUSES
b 08
Pressure switch circuit open
• Blockage in intake or vent system.
• Vent and/or intake system not constructed in accordance with Part VI.
• Blocked or leaking pressure switch tubing
• Heat exchanger or burner blockage
• Terminals exposed to high winds
• Blockage in condensate trap above vent.
b 18
MCBA supply sensor detected temperatures in excess
of 200°F
• Heating load at time of error was far below the minimum
fi
ring rate of the
boiler
• Defective primary pump or no
fl
ow in primary loop (Piping Method 1)
• Control system miswired so that boiler operation is permitted when no
zones are calling
b 19
MCBA return sensor detected temperatures in excess
of 200°F
• See possible causes for “b18”
• Flow through boiler reversed
• Sensor wiring reversed
b 24
MCBA is reading a return sensor temperature higher
than the supply sensor temperature. Condition must be
present for at least 75s for this error code to appear.
• Flow through boiler reversed. Verify correct piping and pump orientation.
• No boiler water
fl
ow. Verify that system is purged of air and that
appropriate valves are open.
• Sensor wiring reversed.
• Supply or return sensor defective.
b 25
Supply water temperature has risen too quickly
• See possible causes for “b18”
• Inadequate boiler water
fl
ow. Verify that pump is operating and that pump
and piping are sized per Part VIII of this manual
b 26
Boiler safety limit, or external limit wired across
terminals 3&4, is open.
• See possible causes for “b18”
• Defective supply sensor.
b 30
Temperature rise between supply and return is too high.
• Inadequate boiler water
fl
ow. Verify that pump is operating and that pump
and piping are sized per Part VIII of this manual
b 61
Pressure switch circuit closed with fan off
• Blockage in pressure switch hose
• Pressure switch wires shorted together
• Defective pressure switch
• Loose or miswired fan speed harness (if “b61” error code is observed
while fan is running)
b 65
Fan is not achieving set point speed
• Loose or incorrect fan speed control connection
• Defective fan
B. Trouble shooting problems where a soft lockout code is displayed. When a soft lockout occurs, the boiler will shut down
and the display will alternate between the number “9” and the letter “b” followed by a two digit service code. The boiler
will automatically restart once the condition that caused the lockout is corrected.
Summary of Contents for FREEDOM FCM120
Page 8: ...8 Figure 5 1 Wall Mounting Hole Locations ...
Page 9: ...9 Figure 5 2 Boiler Mounting Hardware ...
Page 11: ...11 Figure 6 1 Boiler Installed In A Confined Space Ventilation Air From Inside ...
Page 31: ...31 Figure 7 21 Condensate Piping Arrangement ...
Page 44: ...44 Figure 10 1 Wiring Connections Diagram ...
Page 45: ...45 Figure 10 2 Ladder Diagram ...
Page 46: ...46 Figure 10 3 Wiring of Isolation Relay for Control of Two Heating Circulators ...
Page 49: ...49 FCM Series Lighting and Operating Instructions ...
Page 55: ...55 FIGURE 12 2 BASIC MENU TREE ...
Page 64: ...64 ...
Page 66: ...66 ...
Page 68: ...68 ...
Page 69: ...69 ...
Page 70: ...70 ...
Page 72: ...72 150 151 152 153 154 155 ...
Page 73: ...73 156 157 158 159 160 161 ...
Page 74: ...74 162 ...
Page 75: ...75 NOTES ...
Page 78: ...78 NOTES ...
Page 79: ...79 NOTES ...
Page 80: ......