51
11) Perform a combustion test. Boilers equipped with a concentric vent system have a
fl
ue gas sample tap located in the
boiler vent collar (under the screw cap). For other vent systems, the sample probe may be inserted into the terminal.
If this is not possible, remove the
fl
ue temperature sensor and insert the analyzer probe in the sensor opening. For the
boiler to operate, this sensor will need to be remain connected to the wiring. If the
fl
ue gas sensor is removed, be sure to
replace it after combustion testing is complete.
Check
CO
2
(or O
2
) and CO at both high and low
fi
re. The boiler may be temporarily locked into high or low
fi
re for 15
minutes as follows:
a) To lock the boiler in high
fi
re, simultaneously press and hold the “Mode” button and “+“ button until the display
fl
ashes “H”, indicating that the boiler has been driven to high
fi
re. After this happens, allow the boiler to operate for
approximately 5 minutes before taking combustion readings.
b) To lock the boiler in low
fi
re, simultaneously press and hold the “Mode” button and “-“ button until the display
fl
ashes “L”, indicating that the boiler has been driven to low
fi
re. After this happens, allow the boiler to operate for
approximately 5 minutes before taking combustion readings.
c) Normal modulation of the boiler should return 15 minutes after the boiler is locked in high or low
fi
re.
At both high and low
fi
re, CO readings should be less than 75 PPM. Typical CO
2
readings are shown in Table 11.3.
Figure 11.2: Gas Valve Detail
Model
Fuel
%CO
2
%O
2
FCM120 Natural Gas
9.5
4.3
FCM120
Propane
10.5
5.0
TABLE 11.3: TYPICAL CO
2
/O
2
COMBUSTION
READINGS RANGE
Summary of Contents for FREEDOM FCM120
Page 8: ...8 Figure 5 1 Wall Mounting Hole Locations ...
Page 9: ...9 Figure 5 2 Boiler Mounting Hardware ...
Page 11: ...11 Figure 6 1 Boiler Installed In A Confined Space Ventilation Air From Inside ...
Page 31: ...31 Figure 7 21 Condensate Piping Arrangement ...
Page 44: ...44 Figure 10 1 Wiring Connections Diagram ...
Page 45: ...45 Figure 10 2 Ladder Diagram ...
Page 46: ...46 Figure 10 3 Wiring of Isolation Relay for Control of Two Heating Circulators ...
Page 49: ...49 FCM Series Lighting and Operating Instructions ...
Page 55: ...55 FIGURE 12 2 BASIC MENU TREE ...
Page 64: ...64 ...
Page 66: ...66 ...
Page 68: ...68 ...
Page 69: ...69 ...
Page 70: ...70 ...
Page 72: ...72 150 151 152 153 154 155 ...
Page 73: ...73 156 157 158 159 160 161 ...
Page 74: ...74 162 ...
Page 75: ...75 NOTES ...
Page 78: ...78 NOTES ...
Page 79: ...79 NOTES ...
Page 80: ......