Method 2: Direct Connection to Heating System (Generally NOT Recommended)
The FCM can be connected directly to the heating system as is done with conventional boilers (Figure 9.8). If
this is done, the
fl
ow rate through the boiler will equal the
fl
ow rate through the system. The
fl
ow rate through the
system must therefore always remain within the limits shown in Table 9.1. For this reason, the pressure drop through
the entire system must be known, added to the boiler pressure drop, and a circulator selected which will provide the
required
fl
ow at the total calculated pressure drop.
This method is generally not recommended because it is often very dif
fi
cult to accurately calculate the pressure
drop through the system. In replacement installations, it may be impossible to get an accurate measurement of the
amount of piping and number of
fi
ttings in the system. In addition, if the system is zoned, the system
fl
ow may drop
well below the minimum required when only one zone is calling for heat.
The one advantage to this method is its installation simplicity. It may make sense to use this method when the
boiler is to be installed with a new single zone system having a low-pressure drop. Pressure drop curves for the
FCM Series boilers are shown in Figure 9.9. Calculation of the system pressure drop, and selection of the
circulator, must be performed by someone having familiarity with pressure drop calculations, such as an HVAC
engineer.
TABLE 9.7: FITTING EQUIVALENT LENGTHS
FITTING
PIPE SIZE
EQUIVALENT LENGTH (ft)
90 ELBOW
1
2.75
TURN IN TEE
1
5.50
RUN OF TEE
1
1.75
SWING CHECK
1
7.00
GATE VALVE
1
0.60
Figure 9.8: Piping Method #2 - Direct Connection of Boiler to Heating System
Summary of Contents for FREEDOM FCM120
Page 8: ...8 Figure 5 1 Wall Mounting Hole Locations ...
Page 9: ...9 Figure 5 2 Boiler Mounting Hardware ...
Page 11: ...11 Figure 6 1 Boiler Installed In A Confined Space Ventilation Air From Inside ...
Page 31: ...31 Figure 7 21 Condensate Piping Arrangement ...
Page 44: ...44 Figure 10 1 Wiring Connections Diagram ...
Page 45: ...45 Figure 10 2 Ladder Diagram ...
Page 46: ...46 Figure 10 3 Wiring of Isolation Relay for Control of Two Heating Circulators ...
Page 49: ...49 FCM Series Lighting and Operating Instructions ...
Page 55: ...55 FIGURE 12 2 BASIC MENU TREE ...
Page 64: ...64 ...
Page 66: ...66 ...
Page 68: ...68 ...
Page 69: ...69 ...
Page 70: ...70 ...
Page 72: ...72 150 151 152 153 154 155 ...
Page 73: ...73 156 157 158 159 160 161 ...
Page 74: ...74 162 ...
Page 75: ...75 NOTES ...
Page 78: ...78 NOTES ...
Page 79: ...79 NOTES ...
Page 80: ......