23
Start-up
1 2 3 4
ON DIP
Communications
interface
LED 1
LED 2
DIP Switches
Button 1
Button 2
Fig. 19: Automatic adjustment X.TUNE
→
Insert micro USB plug in communications interface.
→
Establish connection to PC with USB-büS interface set.
→
Starting Bürkert Communicator.
→
Implementing settings.
10.3.2 Connecting büS device with Bürkert
Communicator
Required components:
•
Communications software: Bürkert Communicator for PC
•
USB-büS interface set (see accessories)
→
Establish connection to PC with USB-büS interface set.
→
Starting Bürkert Communicator.
→
Implementing settings.
10.4 IO-Link
10.4.1 Information, IO-Link
IO-Link is an internationally standardized IO technology (IEC
61131-9) to enable sensors and actuators to communicate.
IO-Link is a point-to-point communication with 3-wire connection
technology for sensors and actuators and unshielded standard
sensor cables.
To ensure clear communication, the IO-Link devices should not
be parameterised simultaneously by the higher-level controller
(PLC) via the IO-Link master and with the Bürkert Communicator
(via the service
10.4.2 interface).Technical specifications, IO-Link
IO-Link specifications
V1.1.2
Supply
via IO-Link (M12 x 1, 5-pin, A-coded)
Port Class
B
SIO mode
no
IODD file
see Internet
VendorID
0x0078, 120
DeviceID
see IODD file
ProductID
8694
Transmission speed
COM3 (230.4 kbit/s)
PD Input Bits
80
PD Output Bits
40
M-sequence Cap.
0x0D
Min. cycle time
5 ms
english