10
Technical data
Digital input
0 – 5 V = log “0”,
12 – 30 V = log “1”
inverted input in reverse order
Communications
interface
Connection to PC via USB bus
interface set
Communication
software
Bürkert Communicator
6.8.2
Electrical data, IO-Link
Protection class
III as per DIN EN 61140
(VDE 0140-1)
Connection
Circular plug-in connector
M12 x 1, 5-pin, A-coded, Port
Class B
Operating voltage
System supply (Pin 1+3)
24 V DC ±25 %
(according to specification)
Actuator supply (Pin 2+5)
1)
24 V DC ±25 %
(according to specification)
Current consumption
System supply (Pin 1+3)
max. 50 mA
Actuator supply (Pin 2+5) max. 100 mA
Total power consumption
max. 3,5 W
1) Actuator supply is galvanically isolated from system supply in accor-
dance with IEC 60664 and for electrical safety in accordance with
SELV from IEC 61010-2-201
6.8.3
Electrical data, büS
Protection class
III as per DIN EN 61140
(VDE 0140-1)
Connection
Circular plug-in connector M12 x 1,
5-pin, A-coded
Operating voltage
24 V DC ±25 %
Current consumption
max. 150 mA
Total power consumption max. 3.5 W
6.9
Factory settings
Function
Parameter
Value
CUTOFF
Sealing function below
Sealing function above
2 %
98 %
CHARACT
Characteristic correction
FREE
2)
DIR.CMD
Reversal of the effective
direction set-point value
Off
Tab. 1: Functions
Additional functions are described in the operating
instructions Type 8694 REV.2.
These instructions can be found on the Internet at
2)
Without change to the settings via the communications software a
linear characteristic is stored in FREE.
english
Type 8694 REV.2