Electrical installation
Type 8098 FLOWave L
WARNING
Risk of injury due to unintentional switch on of the power supply or uncontrolled restart of the
installation.
▶
Take appropriate measures to avoid unintentional activation of the installation.
▶
Guarantee a set or controlled process restart after carrying out any intervention on the device.
CAUTION
Risk of injury due to a heavy device.
A heavy device can fall down during transport or during installation and cause injuries.
▶
Transport, install and dismantle a heavy device with the help of another person.
▶
Use appropriate tools.
NOTICE
The device will be damaged if you use a tool to turn the blind cover or the display module.
▶
Do not use a tool to turn the blind cover or the display module.
NOTICE
If you try to remove the nut from a stainless steel M20x1.5 cable gland, the device is no longer tight.
▶
Do not remove the nut of a stainless steel M20x1.5 cable gland. The nut of a stainless steel M20x1.5
cable gland cannot be removed.
▶
Turn the nut until the stop. If you turn beyond the stop, the cable gland unscrews from the device and
the device is no longer tight.
NOTICE
If the screwed plug of a 5-pin M12 male connector is removed, the device is not tight.
▶
If the 5-pin M12 male connector is not used, do not remove the screwed plug.
▶
Screw the plug to the 5-pin M12 male connector to a torque of 2 Nm (1.47 ft·lbf).
NOTICE
If the screwed plug of a 4-pin M12 female connector is removed, the device is not tight.
▶
If the 4-pin M12 female connector is not used, do not remove the screwed plug.
▶
Screw the plug to the 4-pin M12 female connector to a torque of 1.3 Nm (0.96 ft·lbf).
NOTICE
The device with M20x1.5 cable glands is not tight if a cable gland is not used
▶
Make sure the unused M20x1.5 cable glands are sealed with the supplied plugs.
▶
When the blind plug is inserted, screw the cable-gland nut in stainless steel to a torque of 3 Nm
(2.21 ft·lbf).
▶
When the blind plug is inserted, screw the cable-gland nut in nickel plated brass to a torque of 8 Nm
(5.90 ft·lbf).
•
Use a high quality electrical power supply, filtered and regulated.
• Do not install the cables near high voltage or high frequency cables; if this cannot be avoided,
observe a minimum distance of 30 cm.