8
Warning
Risk of injury due to improper installation.
▶
Installation may only be performed with trained technical personnel
with suitable tools.
▶
Secure the system against unintentional activation.
▶
Following installation, ensure a controlled restart.
5.1
Fluidic installation
Installation position: any, preferably solenoid facing upward.
→
Check pipelines for soiling and clean if required.
→
Install a dirt trap to protect against disruptions (mesh width:
0.2–0.4 mm).
Note flow direction. Letters on the housing indicate the flow
direction: from 1(P)
→
2(A).
5.1.1
Devices with threaded connection
note
Caution: risk of breakage.
▶
Do not use the solenoid as a lever arm.
→
Seal the thread with PTFE tape.
→
Hold the device on the housing using an open-end wrench and
screw into the pipeline.
5.1.2
Devices with flange connection
→
Remove protective cover.
→
Loosen nut and remove solenoid.
Warning
Risk of injury due to medium leak.
▶
Ensure that the seals provided fit the valve properly.
▶
Ensure that the manifold is level.
▶
Ensure sufficient surface quality of the manifold.
→
Insert the seal into the housing.
→
Screw the housing onto the manifold, observing the maximum
tightening torque of 1 Nm.
English