Option: Rotary actuators with inte-
grated emergency reset
Description of lED status
lED
status
Description
Green
lit
Mains power operation
flashing
Battery operation
Red
lit
Battery is charged
flashing
Battery is charging
installation of emergency reset into the
9.4.
rotary
actuator
4 fastening screws ST2.2 x 6.5
Fig. 19: Illustration: installation of emergency reset into the rotary actuator
Fasten the safety block of the emergency current model onto the
→
rotary actuator with 4 (see illustration
Fig. 19:
).
Connect the battery in this order:
→
1. F+ (wire color red)
2. E- (wire color black)
Connect the power supply in this order:
→
1. terminal 18
2. terminal 17
(see
Fig. 18:Illustration: Electronic printed circuit board