22
Operation and function
status
description
3 pulses every 3 s
The valve current is too high. This means
that an incorrect valve was installed or there
is a short-circuit.
4 pulses every 3 s
No motor contactor is connected.
(4
6 pulses every 3 s
The fuse for the valve current is defective.
Troubleshooting
Table 3:
4)
The fault “No motor contactor is connected” is indicated in non-
switched status only. This means that this fault is only indicated if
there is no frequency at the gasoline pulse input.
3)
The fault “The valve current is too low” is indicated in switched status
only.
fuses
8.3.
The device features two fuses
The main fuse (F2) is a self-resetting fuse with a nominal value of 1.1A;
it monitors the total power consumption of the device.
The second fuse (F1) is a fast-acting fuse (5 x 20 mm) in accordance
with the standard IEC 60127-2-1, with a disconnect threshold of 1500
A. Its nominal value is 800 mA; it monitors the valve current.
The electronics monitor the reliability performance of the fuse and
indicate a malfunction with the red LEDs on both sides (6 pulses
every 3 s).
Fuse F1
Valve current monitor
5 x 20 mm, 800 mA, fast-acting)
Fuse F2
Main fuse, monitoring the total
power
Position of the fuses
Fig. 10:
English
Type 1094 EV
Summary of Contents for 1094 EV
Page 4: ...4 11 Packaging Transport 26 12 Storage 27 13 Disposal 27 English Type 1094 EV ...
Page 28: ...28 English Type 1094 EV ...
Page 30: ...30 11 Verpackung Transport 52 12 Lagerung 53 13 Entsorgung 53 Typ 1094 EV deutsch ...
Page 54: ...54 Entsorgung Typ 1094 EV deutsch ...
Page 80: ...80 Type 1094 EV français ...
Page 81: ......
Page 82: ...www burkert com ...