15
Technical Data
frequency inputs / gasoline pulses
6.5.1.
The volumetric flow of the delivered gasoline is measured by the piston
meter, converted into a frequency-proportional clock signal by the
gasoline pump computer and switched to the frequency input of the
controller (
In the controller this clock signal is processed as the actual value of
the volumetric flow of the gasoline.
High-level pulse:
3.4 V – 26 V
Low-level pulse:
0 V – +0,9 V
Input resistance:
> 10 k
Ω
Max. input current:
5 mA
Min. pulse duration: 400 µs
Measurement rate:
1 measurement/0.75 s
Resolution:
1 Hz
Measuring range:
0 ... 51 l/min
Pulse rate:
Can be adjusted via manual control unit from
31 – 200 pulses/liter
Input
terminals
for gasoline
pulse
5 V
Input to the
controller
Jumper
(1
C03 / C05
GND
Fig. 4: Frequency input of the controller Type 1094 EV
(1
The Jumper C0 (C03 for side 1 and C05 for side 2) can be used
to switch the input from “open emitter” to “open collector”.
English
Type 1094 EV