120V~/60Hz Pump:
Spas equipped with a 120V~/60Hz pump can be
120V~/60Hz Cord-Connected, 120V~/60Hz, Permanently-Connected, or
240V~/60Hz Permanently-Connected.
120V~/60Hz Cord- Connected Installation:
This option is only applicable
if the spa was ordered from the factory with both a 120V~/60Hz pump and a
120V~/60Hz power cord. The spa’s Safety Approval Listing and warranty will
be void, and the spa may be unsafe if an aftermarket power cord is installed
on the spa. Cord-Connected spas have already been converted to operate on
120V~/60Hz power at the factory and come with approximately 15‘ (4.57m)
of useable power cord (the maximum length allowed) attached to the spa. This
factory installed power cord comes with a built-in GFCI breaker.
IMPORTANT:
Cordage shall be replaced only with a special cordage as-
sembly available from the manufacturer, its service agent, or similarly qualified
persons in order to avoid a hazard.
Cord-Connected 120V~/60Hz spas require that the factory installed power
cord, with its built-in GFCI breaker be connected to a 120V~/60Hz, 20A,
Single-Phase, dedicated, grounded circuit and power outlet. It is important that
this circuit is dedicated (not being used by any other electrical appliance) or your
spa may not function properly. For safety purposes, the location of the power
outlet (where the spa is to be connected) can be no closer than the minimum
allowable distance specified by the national and local wiring rules in your area.
Installation must be in accordance with all national and local wiring rules.
Fill Spa before Powering on:
Always fill the spa to the recommended level
before turning on the power (see Pre-fill Checklist).
Residual Current Device:
The appliance should be supplied through a
residual current device with a rated tripping current not exceeding 30mA.
WARNING:
Never use an extension cord. Bullfrog International, LC does
not allow the use of an extension cord under any possible situation. The use of an
extension cord voids any warranty on the spa equipment and also exposes the
consumer to additional risk of fire, electrical shock, injury, or death.
120V~/60Hz Permanently-Connected Installation:
Unless your spa was
ordered from the factory with a 120V~/60Hz power cord, its equipment is
configured to operate on 240V~/60Hz power (even though it was equipped
with a 120V~/60Hz pump). Prior to the 120V~/60Hz electrical installation,
the spa’s equipment will need to be converted from its 240V~/60Hz
configuration to a 120V~/60Hz configuration. For specific conversion instruc-
tions, please refer to the system wiring diagram inside the Control System Box
(located in the spa’s equipment compartment).
Permanently-Connected 120V~/60Hz spas require a GFCI protected, 3-wire
(Line 1, Neutral and Ground), 120V~/60Hz, 20A, Single-Phase, dedicated
electrical circuit. It is important that this circuit is dedicated (not being used
by any other electrical appliance) or the spa may not function properly. Instal-
lation must be in accordance with all national and local wiring rules.
240V~/60Hz Permanently -Connected Installation:
Even though the spa is
equipped with a 120V~/60Hz pump, it has already been configured to operate on
240V~/60Hz power unless the spa came with a factory connected 120V~/60Hz
power cord, in which case the spa’s equipment will need to be converted from its
120V~/60Hz configuration to the 240V~/60Hz configuration. For specific con-
version instructions, please refer to the system wiring diagram inside the Control
System Box (located in the spa’s equipment compartment).
Permanently-Connected 240V~/60Hz spas require a GFCI protected, 4-wire
(Line 1, Line 2, Neutral, and Ground), 240V~/60Hz, 50A, Single-Phase, dedi-
cated electrical circuit. It is important that this circuit is dedicated (not being used
by any other electrical appliance) or the spa may not function
properly. Installation must be in accordance with all national and local wiring rules.