Installation Operation Maintenance Manual is Subject to Change without Notice- Last Revised June 2018 

 

13 

BULLDOG SideWinder – Installation, Operation, and Maintenance Manual 

 

 
 

e.   If during compressor operation the condenser leaving temperature rises above 

140

°

F, compressor operation will be disabled. After 10 minutes an auto reset 

occurs and the compressor will be enabled as soon as the temperature drops 
below 120

°

F. The outgoing system fluid sensor is mounted on the leaving fluid 

pipe. Actual compressor restart will be delayed a minimum of 5 minutes by the 
anti-recycle timer. A flash code of 3 will be initiated upon a high outgoing system 
fluid temperature shutdown. 

f.  If the discharge air temperature drops below 40

°

F, compressor operation will 

be disabled. After 10 minutes an auto reset occurs and the compressor will be 
enabled as soon as the temperature rises above 55

°

F. The discharge air 

temperature sensor is mounted on the fan housing. Actual compressor restart 
will be delayed a minimum of 5 minutes by the anti-recycle timer. A flash code 
of 4 will be initiated upon a low discharge air temperature shutdown. 

g.    The condensate level sensor is a 100 ohm thermistor that is heated for 15 

seconds every 4 minutes. Its temperature is measured at the beginning of the 
heat cycle, and again at the end of the heating cycle. If the condensate level 
rises above the sensor it will not warm up during the warm up cycle, and the 
temperature change will be insignificant. It is this lack of temperature change 
that the controller sees as an impending condensate overflow. When high 
condensate level is detected, compressor operation is immediately terminated, 
and at the same time the fan is stopped for 30 seconds, and then restarted. At 
this time a flash code of 7 will be initiated. The 4 minute cycle will continue until 
the cooling call is no longer in place. If the condensate level drops below the 
sensor, compressor operation will be returned to normal. However, if the 
condensate level stays above the sensor for more than 15 minutes, the fault 
alarm will be triggered. This fault signal will automatically reset once the 
condensate level goes below the sensor. 

 

Note: The last flash code will be maintained in memory for 1 week or until the unit controls are 
powered down. The flash code will continue until the problem has cleared and the compressor has 
been put into operation. If a cooling call is in place, it must be disengaged before the cause of the 
last alarm shutdown can be identified. 

Summary of Contents for SideWinder SWD008

Page 1: ...ce Manual is Subject to Change without Notice Last Revised June 2018 Installation Operation Maintenance BULLDOG SideWinder Heat Pump Only qualified personnel should install service and repair the equi...

Page 2: ...19 Before calling technical support please have the model and serial number of the unit ready For Parts For replacement parts please call your local Bulldog Representative with the model and serial nu...

Page 3: ...ctrical components ONLY trained and qualified personnel should install repair or service the equipment WARNING The installation of the SideWinder Heat Pump and all associated components parts and acce...

Page 4: ...he unit in an upright position may result in permanent damage to the unit Dropping the unit or exposing it to extreme shock or vibration may also result in permanent damage to the interior components...

Page 5: ...teps required to successfully install a SideWinder unit 1 Remove packaging and inspect the unit Check for shipping damage or material shortage file a freight claim and notify your sales representative...

Page 6: ...y with all applicable codes and regulations It is the responsibility of the installing contractor to ensure adequate service clearance for regular maintenance or for repair in place is exercised The i...

Page 7: ...Installation Operation and Maintenance Manual INSTALLATION STEPS 1 Screw discharge plate onto hanging bracket prior to mounting Unscrew the front stop screws on the flanges of the hanging bracket whi...

Page 8: ...ensure the edge of the hinged panel is flush with the finished wall when closed Figure 4 Vertical distance is to be a minimum of 3 4 from the top of the hanging bracket This alignment will ensure the...

Page 9: ...odes and regulations DO NOT bend or kink supply lines or hoses If supplied Supply and return ultra flex hoses 3 4 available from the factory are fitted with swivel joint fittings at one end to allow r...

Page 10: ...ance Manual is Subject to Change without Notice Last Revised June 2018 8 BULLDOG SideWinder Installation Operation and Maintenance Manual WIRING 1 Wire room thermostat to electrical panel as indicated...

Page 11: ...and do not operate units during the construction process The BULLDOG Heat Pump provides year round cooling and heating as controlled by the unit thermostat or by a direct digital controller The BULLDO...

Page 12: ...tat terminal Cool Call Y on thermostat terminal Fan Call G on thermostat terminal Auxiliary A on thermostat terminal Compressor shutdown 24V AC signal thru O O Providing a continuous 24V potential to...

Page 13: ...Power ON timer Compressor operation is delayed for approximately 5 minutes after restoration of power This prevents all units from coming on line at the same time when power is restored It also preve...

Page 14: ...e set to alarm however if the open switch closes within 10 minutes a restart cycle is initiated The restart cycle begins with a 10 minute delay after which if there is a cool call in place and all oth...

Page 15: ...nsate level sensor is a 100 ohm thermistor that is heated for 15 seconds every 4 minutes Its temperature is measured at the beginning of the heat cycle and again at the end of the heating cycle If the...

Page 16: ...esent day thermostats operate in this manner there are others that may or may not work properly The following should be checked out for satisfactory performance prior to installation 1 Heat Pump Therm...

Page 17: ...board 24V power This capability allows unit or compressor shutdown based on a door switch a light switch or occupancy switch A separate 24V power supply is required if two or more units are being shut...

Page 18: ...xtend the life of the hoses heat exchangers and other water side accessories WATER FLOW RATE Open all isolation valves to the unit Ensure that the entering and leaving fluid temperatures of the BULLDO...

Page 19: ...unit Disconnects are usually within reach of the unit Exercise caution at all times Inspect the fan section to ensure that it is clear of any debris and that the fan rotates freely BULLDOG 008 060 uni...

Page 20: ...LLDOG SideWinder Installation Operation and Maintenance Manual START UP To register the unit warranty proper start up is required by a factory approved technician The following items must be recorded...

Page 21: ...ed load amps by more than 10 percent of the values noted on the unit nameplate SAFETY CONTROL RESET All BULLDOG Heat Pumps include high and low pressure switches to prevent the machine from operating...

Reviews: