COOL OPERATION

 

1.   Monitoring of the refrigerant cycle continues during operation of the compressor. The 

following malfunctions will cause the compressor to shutdown: 

a.   If the head pressure exceeds the set point of the high pressure switch, the switch 

will open and the control board will terminate the compressor operation within 
10 seconds. At this time a flash code of 6 will be initiated on the red diagnostic 
LED 15. Compressor operation will be restored in accordance with the 
“Intelligent reset” algorithm. 

b.   If the suction pressure drops below the set point of the low pressure switch, the 

switch will open and if it remains open beyond the 1 minute ignore period after 
start up, compressor operation will be terminated within 10 seconds. 
Compressor operation will be restored in accordance with the “Intelligent Reset” 
algorithm. A flash code of 5 on the red diagnostic LED will be initiated at this 
time. 

c.    Intelligent Reset Algorithm – If a low or high pressure switch opens and remains 

open for more than 10 minutes, a hard lockout will be initiated and the cooling 
mode will be locked off until the controls are manually reset. At the same time 
the fault relay K3 will be set to alarm; however, if the open switch closes within 
10 minutes a restart cycle is initiated. The restart cycle begins with a 10 minute 
delay after which if there is a cool call in place and all other enablers are within 
the start parameters, the compressor will again be put into operation. Should 
either of the pressure switches open again, the shutdown procedure will cycle 
again, followed by a restart. The intelligent reset will allow two open switch 
shutdowns and restarts in a 24 hour period. If a third shutdown occurs within 
24 hours this will put the refrigeration system into a full and hard lockout, 
requiring a power down to reset. If two or less switch open shutdowns occur 
within a 24 hour period, they will be erased from memory and will not 
contribute to a future hard lockout. (A hard lockout will prevent compressor 
operation until the controls are powered down for at least 20 seconds, and the 
green power light goes out. A soft lockout is a compressor shutdown that will 
be restored once the condition causing the shutdown returns to normal.) 

d.   During compressor operation, refrigerant temperature, system fluid temperature 

and discharge air temperature are continuously monitored. If the refrigerant 
temperature 
drops below 40

°

F, compressor operation will be disabled. After 10 

minutes an auto reset occurs and the compressor will be enabled as soon as the 
temperature rises above 65

°

F. Actual compressor restart will be delayed a 

minimum of 5 minutes by the anti-recycle timer. A flash code 
of 2 will be initiated upon a low refrigerant temperature shutdown. 

Summary of Contents for SideWinder SWD008

Page 1: ...ce Manual is Subject to Change without Notice Last Revised June 2018 Installation Operation Maintenance BULLDOG SideWinder Heat Pump Only qualified personnel should install service and repair the equi...

Page 2: ...19 Before calling technical support please have the model and serial number of the unit ready For Parts For replacement parts please call your local Bulldog Representative with the model and serial nu...

Page 3: ...ctrical components ONLY trained and qualified personnel should install repair or service the equipment WARNING The installation of the SideWinder Heat Pump and all associated components parts and acce...

Page 4: ...he unit in an upright position may result in permanent damage to the unit Dropping the unit or exposing it to extreme shock or vibration may also result in permanent damage to the interior components...

Page 5: ...teps required to successfully install a SideWinder unit 1 Remove packaging and inspect the unit Check for shipping damage or material shortage file a freight claim and notify your sales representative...

Page 6: ...y with all applicable codes and regulations It is the responsibility of the installing contractor to ensure adequate service clearance for regular maintenance or for repair in place is exercised The i...

Page 7: ...Installation Operation and Maintenance Manual INSTALLATION STEPS 1 Screw discharge plate onto hanging bracket prior to mounting Unscrew the front stop screws on the flanges of the hanging bracket whi...

Page 8: ...ensure the edge of the hinged panel is flush with the finished wall when closed Figure 4 Vertical distance is to be a minimum of 3 4 from the top of the hanging bracket This alignment will ensure the...

Page 9: ...odes and regulations DO NOT bend or kink supply lines or hoses If supplied Supply and return ultra flex hoses 3 4 available from the factory are fitted with swivel joint fittings at one end to allow r...

Page 10: ...ance Manual is Subject to Change without Notice Last Revised June 2018 8 BULLDOG SideWinder Installation Operation and Maintenance Manual WIRING 1 Wire room thermostat to electrical panel as indicated...

Page 11: ...and do not operate units during the construction process The BULLDOG Heat Pump provides year round cooling and heating as controlled by the unit thermostat or by a direct digital controller The BULLDO...

Page 12: ...tat terminal Cool Call Y on thermostat terminal Fan Call G on thermostat terminal Auxiliary A on thermostat terminal Compressor shutdown 24V AC signal thru O O Providing a continuous 24V potential to...

Page 13: ...Power ON timer Compressor operation is delayed for approximately 5 minutes after restoration of power This prevents all units from coming on line at the same time when power is restored It also preve...

Page 14: ...e set to alarm however if the open switch closes within 10 minutes a restart cycle is initiated The restart cycle begins with a 10 minute delay after which if there is a cool call in place and all oth...

Page 15: ...nsate level sensor is a 100 ohm thermistor that is heated for 15 seconds every 4 minutes Its temperature is measured at the beginning of the heat cycle and again at the end of the heating cycle If the...

Page 16: ...esent day thermostats operate in this manner there are others that may or may not work properly The following should be checked out for satisfactory performance prior to installation 1 Heat Pump Therm...

Page 17: ...board 24V power This capability allows unit or compressor shutdown based on a door switch a light switch or occupancy switch A separate 24V power supply is required if two or more units are being shut...

Page 18: ...xtend the life of the hoses heat exchangers and other water side accessories WATER FLOW RATE Open all isolation valves to the unit Ensure that the entering and leaving fluid temperatures of the BULLDO...

Page 19: ...unit Disconnects are usually within reach of the unit Exercise caution at all times Inspect the fan section to ensure that it is clear of any debris and that the fan rotates freely BULLDOG 008 060 uni...

Page 20: ...LLDOG SideWinder Installation Operation and Maintenance Manual START UP To register the unit warranty proper start up is required by a factory approved technician The following items must be recorded...

Page 21: ...ed load amps by more than 10 percent of the values noted on the unit nameplate SAFETY CONTROL RESET All BULLDOG Heat Pumps include high and low pressure switches to prevent the machine from operating...

Reviews: