Revision 0.1 [05/10/18]
Page 4
Performance
Heating: 47F Outside, 68F Inside
Heating Capacity (Btu/h)
4731 (recirc)*
6531 (vent)**
Heating Efficiency (COP)
(excludes fan power - see below)
3.6 (recirc)
4.8 (vent)
Heating Elec Power (W)
(excludes fan power - see below)
379 (recirc)
399 (vent)
Heating: 32F Outside, 68F Inside
Heating Capacity (Btu/h)
3702 (recirc)
6789 (vent)
Heating Efficiency (COP)
(excludes fan power - see below)
3.3 (recirc)
5.4 (vent)
Heating Elec Power (W)
(excludes fan power - see below)
331 (recirc)
366 (vent)
Heating: 17F Outside, 68F Inside
Heating Capacity (Btu/h)
2674 (recirc)
7046 (vent)
Heating Efficiency (COP)
(excludes fan power - see below)
2.8 (recirc)
6.2 (vent)
Heating Elec Power (W)
(excludes fan power - see below)
283 (recirc)
332 (vent)
Cooling: 95F(DB)/75F(WB) Outside, 80F(DB)/67F(WB) Inside
Cooling capacity (Btu/h)
2230 (recirc)
5314 (vent)
Sensible cooling (Btu/h)
1318 (recirc)
3891 (vent)
Latent cooling (Btu/h)
912 (recirc)
1423 (vent)
Dehumidification (Liters/day)
9.6 (recirc)
14.9 (vent)
Cooling Efficiency (COP)
(excludes fan power - see below)
3.2 (recirc)
7.6 (vent)
Cooling Elec Power (W)
(excludes fan power - see below)
202 (recirc)
204 (vent)
Fans
Total fan power (W)
ECM Fans (heating & cooling)
38.6(50% speed)
98.1(70% speed)
* Recirculation mode heating and cooling capacity is relative to indoor conditions
** Ventilation mode heating and cooling capacity is relative to outdoor air conditions
Summary of Contents for CERV2-6EC
Page 5: ...Revision 0 1 05 10 18 Page 5...
Page 8: ...Revision 0 1 05 10 18 Page 8...
Page 9: ...Revision 0 1 05 10 18 Page 9...
Page 10: ...Revision 0 1 05 10 18 Page 10...
Page 15: ...Revision 0 1 05 10 18 Page 15 Appendix WiFi Setup...
Page 24: ...Revision 0 1 05 10 18 Page 24 Wired Auxiliary Output Example Fan Interlock wiring...
Page 27: ...Revision 0 1 05 10 18 Page 27 Wireless Auxiliary Output Example GEO Boost Configuration...