SCS 104
Moisture detector: automatic reset following moisture ingress
Display →
toP
→
hLtc
(
hLtc
= humidity latch). The setting applies to all connected moisture detectors.
Specifies whether the moisture ingress message must be reset manually or will automatically be re-
set after the sensor dries.
Parameter range:
YES
: The status will be indicated until the user restarts the device and the pumps will be deactivated.
no
: The status message will automatically be cleared. The pumps will be reactivated again once
moisture is no longer detected.
Factory setting:
no
Note:
This menu will be hidden if the menu is locked.
Moisture detector: error cleared automatically after cable break
Display →
toP
→
bLtc
(
bLtc
= broken wire latch). The setting applies to all connected moisture detectors.
Determines whether the cable break alarm must be reset manually or will automatically clear on
valid measuring signal.
Parameter range:
YES
: The status will be indicated until the user restarts the device. Clears the error, and the pumps
will be deactivated.
no
: The error message will disappear. The pumps will be switched on again once the moisture de-
tector is reactivated again.
Factory setting:
YES
Note:
This menu will be hidden if the menu is locked.
Lock Menu
To protect the menu from unauthorised use, enter a value for the lock code. Menu items can then only be accessed after enter-
ing the correct code.
Display →
toP
→
Loc
This setting will cancel/enable the menu lock.
Parameter range:
0 to 9999
Factory setting:
0 (keylock cancelled)
Note:
This menu will be hidden if the menu is locked.
Restart
Display →
toP
→
rESt
(
rESt
= restart)
The device will restart, all settings are saved. All error messages will be reset.
The moisture detector will be reset, irrespective of the settings in menus
h.Itc
and
h.Moi
.
Parameter range:
YES
: Restart. The display will show the software version for the device and returns to measurement
display.
no
: Exit menu without restarting.
Note:
The user settings will be saved.
15
Bühler Technologies GmbH
BECS0031 ◦ 02/2020
Summary of Contents for SCS 104
Page 30: ...SCS 104 9 3 Drawing 1 Flow chart 28 Bühler Technologies GmbH BECS0031 02 2020 ...
Page 34: ......
Page 71: ......
Page 72: ......
Page 73: ......