Nivotemp NT MD
Possible errors
Problem / Malfunction
Possible cause
Action
Switching output not trigger-
ing when exceeding limits
– Switching output configured incorrectly
– In submenu
Cou
x
: “Test Switching Output“ to
ensure normal mode
– Switching output defect
– In submenu
Cou
x
: “Test Switching Output” to
test the desired switching output
Switching output constantly
switching
– Switching output configured incorrectly
– In submenu
Cou
x
: “Test Switching Output“ to
ensure normal mode
– Switching output defect
– In submenu
Cou
x
: “Test Switching Output” to
test the desired switching output
The analogue doesn’t receive
the full/correct output current
– Wrong signal type set
– In submenu
Aou
x
: Check and if necessary set
the correct signal type (current/voltage out-
put)
– Load too high (current output)
– Reduce load to permissible value
Analogue output doesn’t
change the output signal
when the input signal changes
– Analogue output configured incorrectly
– In submenu
CAn
x
: „Test Analogue Output“ to
ensure normal mode
7.2 Spare parts and accessories
Accessories
Item no. 4-pin
Item no. 8-pin
Description
9144 05 0010
9144 05 0048
Connecting cable M12x1, 1.5 m, angular coupling and straight plug
9144 05 0046
9144 05 0049
Connecting cable M12x1, 3.0 m, angular coupling and straight plug
9144 05 0047
9144 05 0033
Connecting cable M12x1, 5.0 m, angular coupling and strands
28
Bühler Technologies GmbH
BE100022 ◦ 11/2020