TC-MIDI (+)
Lock Menu
To protect the menu from unauthorised use, enter a value for the lock code. Menu items can then only be accessed after enter-
ing the correct code.
Display →
toP
→
Loc
This setting will cancel/enable the menu lock.
Parameter range:
0 to 9999
Factory setting:
0 (keylock cancelled)
Note:
This menu will be hidden if the menu is locked.
Modbus RTU baudrate
The default transfer rate is 19200 bps. This can be configured for the specific application within a defined range. The options are
in the display are listed in kbps (19.2 corresponds to 19200 bps). The properties of the digital interface are not affected when re-
setting the device to its factory settings!
This menu item is only available on devices with "Digital output Modbus RTU" option.
Display →
toP
→
baud
Determines the transfer rate for the digital interface.
Parameter range:
4.80
9.60
19.20
38.40
57.60
115.2
Factory setting:
19.20
Note:
This menu will be hidden if the menu is locked.
Modbus RTU parity
The default parity is even/odd, options are odd parity, no parity. The number of stop bits is automatically set based on the re-
spective setting. No parity uses two stop bits, otherwise it is one. The properties of the digital interface are not affected when re-
setting the device to its factory settings!
This menu item is only available on devices with "Digital output Modbus RTU" option.
Display →
toP
→
Pari
This setting restores the factory settings.
Parameter range:
nonE
odd
EVEn
Factory setting:
Even
Note:
This menu will be hidden if the menu is locked.
23
Bühler Technologies GmbH
BE440016 ◦ 07/2022
Summary of Contents for ModbusRTU TC-MIDI
Page 53: ......