
TC-Standard (+)
4.2.3 Connecting the moisture detector (option)
When ordering the cooler with
moisture detector option
, it will be factory installed inside a flow adapter, or for the
filter option
installed and connected in the filter head.
4.2.4 Peristaltic pump connector (optional)
Coolers ordered with attached peristaltic pump already have it installed and wired. Heat exchangers ordered at the same time
are already installed and connected to the peristaltic pump.
The ø6 mm (0.24 inch) hose nipple for the pump’s condensate outlet must be carefully and properly connected with a suitable
hose and hose clamp.
Versions with screw connections DN 4/6 or 1/6”-1/4” are supplied with ferrule and knurled nut and must be carefully sealed
with appropriate hose.
NOTICE
Installing peristaltic
pumps
CPsingle / CPdouble limits the maximum permissible
oper-
ating pressure
in the system!
Operating pressure ≤ 1 bar
4.2.5 Connecting the heat exchanger
The picture on the left shows the schematics for connecting two separate heat exchangers.
To minimise gas wash out in the cooler, the two (identical) heat exchangers must be operated in series (right picture). This
should be done as follows:
1.
Gas inlet line to red gas inlet on heat exchanger 2 (pre-cooling).
2.
Connection between gas outlet on heat exchanger 2 and the red gas inlet on heat exchanger 1 (after-cooling).
3.
Attaching the final gas output line to the gas outlet on heat exchanger 1.
gas out
gas in
gas out
gas in
condensate out
condensate out
Heat exchanger 1
Heat exchanger 2
Gas cooler
(two single heat exchangers)
gas out
gas in
gas out
gas in
condensate out
condensate out
Heat exchanger 1
Heat exchanger 2
Gas
(two heat exchangers in series)
The gas inputs are marked in red.
11
Bühler Technologies GmbH
BE440026 ◦ 12/2020