Boiler installation
7
25
We reserve the right to make any changes due to technical modifications.
Installation and maintenance instructions Logano GA124 special gas-fired boiler • Issue 04/2005
7.6.1 Installation of the wall penetration of a horizontal flue systems
Please read the following instructions and information
on the installation of the wall penetration carefully and
note the safety instructions.
The wall penetration must be installed in the wall as
directed by the regulations and/or local building codes.
z
Make an opening in the wall with a diameter of six (6)
inches at the required position of the wall
penetration.
z
Insert the wall penetration into the wall from the
outside and attach to the outside wall with the four
screws.
z
Insert flue pipe into wall penetration from the outside.
Attach the termination tee horizontally to the flue pipe
and install as directed by the installation instructions
of the flue system manufacturer.
Fig. 21
Wall penetration
Fig. 22
Installing flue pipe
1
Wall penetration
2
Flue pipe
3
End piece of flue pipe (t-piece)
1
2
3