Cat No(s): LN4691KNX - H4691KNX
KNX temperature control panel
12. COMMUNICaTION ObjECTS (CONTINUED)
12.1 list of objects (continued)
No.
Function
Object name
Size
Flags
23
Fan
Fan Speed Auto
1.002 (1 bit)
CTW
Automatic Fan speed sent on the bus
Only if 1-bit Fan function is active
1 = Automatic Fan speed
0 = No Automatic Fan speed (default value)
24
Fan
Fan Speed status (DPT 5.001)
5.001 (1 byte)
CW
Fan speed (%) received by the bus
Only if 1-byte Fan function is active
25
Fan
Fan Speed status (DPT 5.010)
5.010 (1 byte)
CW
Fan speed received by the bus
Only if 1-byte Fan function is active
0 = Fan speed off (default value)
1 = Fan speed 1
2 = Fan speed 2
3 = Fan speed 3
26
Fan
Fan Speed 1 status
1.002 (1 bit)
CW
Fan speed 1 received by the bus
Only if 1-bit Fan function is active
1 = Fan speed 1
0 = Fan speed off (default value)
27
Fan
Fan Speed 2 status
1.002 (1 bit)
CW
Fan speed 2 received by the bus
Only if 1-bit Fan function is active
1 = Fan speed 2
0 = Fan speed off (default value)
28
Fan
Fan Speed 3 status
1.002 (1 bit)
CW
Fan speed 3 received by the bus
Only if 1-bit Fan function is active
1 = Fan speed 3
0 = Fan speed off (default value)
29
Information
Window status
1.002 (1 bit)
CW
Window status received from the bus
Only if 1-bit Fan function is active
1 = Window open
0 = Window closed (default value)
30
Display
Display mode
1.002 (1 bit)
CRW
Only if Par7 = 2 (show both setpoint and measured temperatures)
1 = Show measured temperature
0 = Show setpoint temperature
The default value is set by Par8 (0 = Setpoint, 1 = Measured)
31
Display
Backlight night mode
1.002 (1 bit)
CRW
Only if the option is active in ETS
1 = backlight min (defined by Par1 “intensitymode eco”
0 = backlight max (defined by Par2 “intensitymode normal” (default value)
32
Display
Standby mode
1.002 (1 bit)
CRW
Only if the option is active in ETS
1 = backlight switched off
0 = backlight switched on (default value)