Installation Instructions

THERMIDISTAT

t

CONTROL

TSTAT

NOTE

: Read the entire instruction manual before starting the

installation.
This symbol

indicates a change since the last issue.

PAGE

SAFETY CONSIDERATIONS

1

. . . . . . . . . . . . . . . . . . . . . . . .

INTRODUCTION

1

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

INSTALLATION CONSIDERATIONS

1

. . . . . . . . . . . . . . . . . .

INSTALLATION

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

HUMIDITY CONTROL FEATURES

8

. . . . . . . . . . . . . . . . . . .

OPERATIONAL INFORMATION

11

. . . . . . . . . . . . . . . . . . . .

THERMIDISTAT

TROUBLESHOOTING

12

. . . . . . . . . . . .

THERMIDISTAT CONFIGURATION RECORD

13

. . . . . . . . .

WIRING DIAGRAM

See Thermidistat Wiring Diagrams

. . . . . .

SAFETY CONSIDERATIONS

Read and follow manufacturer instructions carefully. Follow all

local electrical codes during installation. All wiring must conform
to local and national electrical codes. Improper wiring or

installation may damage Thermidistat Control.
Recognize safety information. This is the safety--alert symbol

. When you see this symbol on the equipment and in the

instruction manual, be alert to the potential for personal injury.
Understand the signal words

DANGER

,

WARNING

, and

CAUTION

. These words are used with the safety--alert symbol.

DANGER

identifies the most serious hazards which will result in

severe personal injury or death.

WARNING

signifies a hazard

which could result in personal injury or death.

CAUTION

is

used to identify unsafe practices which would result in minor

personal injury or product and property damage.

NOTE

is used

to highlight suggestions which will result in enhanced
installation, reliability, or operation.

®

A98427

Height (In.)

Width (In.)

Depth (In.)

4---3/8

7---3/8

1---3/8

Fig. 1

---

Bryant Programmable Thermidistat Control

INTRODUCTION

Bryant’s 7--day programmable / non--programmable Thermidistat
Control is a wall--mounted, low--voltage control which combines

temperature and humidity control in a single attractive unit. An
extension of Bryant’s proven line of thermostats, it provides

separate set points for heating and cooling, and now adds

humidification and dehumidification.
Different heating and cooling set points and times are

programmable for 4 periods per day and 7 days per week. The
Thermidistat Control can also be field--configured as a

non--programmable thermostat. When

operating

in

the

non--programmable configuration it will still have both

temperature and humidity control. Humidify and dehumidify

outputs provide direct control of humidity. Batteries are not used.
During power loss an internal memory stores programs and

settings for unlimited time, and the clock continues to run for at
least 8 hr.

INSTALLATION CONSIDERATIONS

A. Power

Note that this control does not require batteries and is not “power

stealing.” It does require 24vac (R and C terminals) of the

low--voltage transformer to be connected to it for proper
operation. It will not operate without these 2 connections.

B. Models

There is a single programmable/non--programmable model for all

applications. It can be configured for AC or HP, 1--or 2--stage

compressor, and for Hybrid Heat

t

installations, allowing it to be

used in place of all Bryant thermostats.

C. Humidify Equipment and Connections

The humidify output connects directly to 24vac operated

humidifiers. No other connection or interlock is required. Any of

several installer--selectable operating modes are available.

ELECTRICAL OPERATION HAZARD

Failure to follow this warning could result in personal

injury or death.
DO NOT connect furnace HUM terminal directly to

Thermidistat ControlHUM terminal. This will bypass

furnace safety controls. See Low Voltage Wiring

Diagrams and notes for proper connection.

!

WARNING

D. Dehumidify Equipment and Connections

The dehumidify output connects to the dehumidify input on

variable--stage

furnaces

and

fan

coils.

Additional

dehumidification is done by controlling the compressor. A variety
of operating modes are available.

E. Outdoor Temperature Sensor

Optimum performance is obtained when an outdoor temperature

sensor is used with the Thermidistat Control. Plan installation so

that 2 wires can be run from Thermidistat Control to an outdoor
location, preferably on the north side of the house or refer to

Installation Instructions included with the outdoor temperature
sensor for simplified connection. Sensor can be mounted to

Summary of Contents for THERMIDISTAT CONTROL TSTAT

Page 1: ...r day and 7 days per week The Thermidistat Control can also be field configured as a non programmable thermostat When operating in the non programmable configuration it will still have both temperature and humidity control Humidify and dehumidify outputs provide direct control of humidity Batteries are not used During power loss an internal memory stores programs and settings for unlimited time an...

Page 2: ...mmed temperature at programmed time TO SET OFF for smart recovery This is factory default ON for conventional recovery D Switch 4 Installer Test Off On Selects a special installer test mode which assists with system startup and checkout See Step 5 System Startup and Check out TO SET OFF for normal operation This is factory default ON for installer test mode STEP 3 Install Thermidistat Control ELEC...

Page 3: ... that option One of these will be flashing The up and down buttons are used both to move between available options and to make selection for each option When option number small display is flashing up and down buttons adjust it moving between available option numbers After desired option number has been selected press SET TIME TEMP button once The large display will now flash indicating that up an...

Page 4: ... is done by supplying blower with a Y signal and no G signal on a call for cooling Not all products with ICM blowers have this feature Check Installation Instructions for ICM air handler used Select OF for normal operation Y and G supplied on a cooling call Select ON for super dehumidification Y with no G on a dehumidify only call Factory default is OF off TO SELECT 1 Enter configuration mode if n...

Page 5: ...the desire of indoor comfort TO SELECT 1 Enter configuration mode if not already there See Step 4 To Enter Configuration Mode Use up and down buttons to make small now flashing display indicate 11 2 Press SET TIME TEMP button once to flash large display 3 Use up or down buttons to move between OF 5 10 15 20 25 30 35 40 45 50 or 55 on large display Factory default is OF 4 Press SET TIME TEMP button...

Page 6: ... the 2 operations Specifically to switch from 1 mode to the other there must be no demand for the old mode and a demand for the new mode and this must exist continually for 20 minutes before transition to the new mode will occur TO SELECT 1 Enter configuration mode if not already there See Step 4 To enter Configuration Mode Use up and down buttons to make small now flashing display indicate 14 2 P...

Page 7: ...P button again to flash upper small display for selection of another option or press END to exit configuration mode REDEFINITION OF BUTTONS Fig 2 shows the original programmable button labels on the left and the redefined non programmable buttons on the right In the figure the buttons are numbered for easy reference They are not numbered on the actual product Six of the buttons numbers 1 through 5...

Page 8: ...ent relative humidity is selected by the homeowner or all humidification can be turned off When humidity in home drops below set point humidifier will be turned on to raise humidity level Humidification can only occur in heating mode HEAT or AUTO HEAT Five different humidification selections are available and are described below 1 Normal Humidify In normal humidify humidifier will be on if there i...

Page 9: ...when compressor turns off In most furnaces and fan coils the blower operates for 90 sec after both Y and G disappear This 90 sec delay should be removed if possible for maximum dehumidification performance Consult furnace or fan coil Installation Instructions to see if delay can be disabled 3 Dehumidify Off Dehumidification can be turned off completely This can be done without changing existing se...

Page 10: ...where the DEHUM terminal is a spade lug located next to the transformer secondary connections See Wiring Diagram Reference Chart and Fig 21 through 24 in Wiring Diagram literature When a dehumidify demand exists relay is de energized and normally closed contacts supply 24vac to the furnace DEHUM terminal As a result the furnace control reduces the blower airflow by 15 percent On newer style variab...

Page 11: ...DIFY AND DEHUMIDIFY INDICATORS The humidity screen selected by pressing the HUMIDITY button uses the same triangles referenced in the above paragraph to indicate the state of the HUM and DHUM outputs When humidification or dehumidification is active the triangle under its set point is turned on AUTO CHANGEOVER When auto changeover mode is selected a change from heat to cool or vice versa will not ...

Page 12: ...ontrol cannot properly read outdoor temperature Check outdoor sensor and its wiring E4 or E5 Internal failure Replace Thermidistat Control E6 System is stuck in defrost Check wiring and heat pump defrost control board Clean Filter icon displayed Filter timer has expired Clean or replace filter and then press VACATION and HOLD END buttons together to reset Cooling or heating will not come on See In...

Page 13: ...ctory default Off or Not Available 9 ______ Intelligent Heat Staging Selection Off or On factory default Off or Not Available 10 ______ HybridHeat Equipment Selection Off or On factory default Off or Not Available 11 ______ Balance Point Setting Off or 5 55 F factory default Off or Not Available 12 ______ Defrost Heat Select 0 1 2 3 factory default 0 or Not Available 13 ______ Room Temperature Off...

Page 14: ...orris St S Indianapolis IN 46231 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No II TSTAT 0 38 Replaces II TSTAT 0 27 Printed in U S A Edition Date 04 06 TSTAT ...

Reviews: