background image

2

outdoor unit and existing control wires may be used for its
connection. Details are provided in sensor instructions.

INSTALLATION

STEP 1

Thermidistat Control Location

Thermidistat Control should be mounted:

S

Approximately 5 ft (1.5m) from floor.

S

Close to or in a frequently used room, preferably on an inside

partitioning wall.

S

On a section of wall without pipes or duct work.

Thermidistat Control should NOT be mounted:

S

Close to a window, on an outside wall, or next to a door

leading to the outside.

S

Exposed to direct light or heat from a lamp, sun, fireplace, or

other temperature--radiating objects which could cause a false
reading.

S

Close to or in direct airflow from supply registers and

return--air registers.

S

In areas with poor air circulation, such as behind a door or in an

alcove.

STEP 2

Set DIP Switches

There is a 4 section DIP switch within the Thermidistat Control
which must be properly set by the installer. It is easiest to set these

4 switches before the Thermidistat Control is mounted to the
wall, so STOP and complete the following steps:

1. Open hinged Thermidistat Control cover.
2. Remove cover completely by snapping it apart at hinge.
3. Open Thermidistat Control by pressing back half of the

right end of plastic case inward while, at the same time,

pulling front and back halves apart at the right end. The 2
halves will swing apart.

4. Snap hinge apart to completely separate the 2 halves.
5. Switches are located in upper right corner of circuit board.

To change switch position, use corner of a small

screwdriver to slide switch to opposite position.

6. After switches have been set, do not reassemble the 2

halves. The rear plastic will first be mounted to the wall.

A. Switch 1—AC/HP Select

Use this switch to select between air conditioner and heat pump

systems.
TO SET:
OFF—for air conditioner installations. This is factory default.

ON—for heat pump installations, using either a fan coil or
furnace (Hybrid Heat).

B. Switch 2—1 Stage/2 Stage

This switch tells the system whether the compressor is 1 or 2
stage.
TO SET:
OFF—for single--stage compressor. This is factory default.

ON—for 2--stage compressors, whether AC or HP.

C. Switch 3—Smart/Conventional Recovery

Selects between conventional and smart recovery from setback.

Conventional recovery changes to new set point at programmed
time. Smart recovery, which is active in both heating and

cooling, starts 90 minutes earlier and smoothly adjusts set point
so room will arrive at programmed temperature at programmed

time.
TO SET:
OFF—for smart recovery. This is factory default.

ON—for conventional recovery.

D. Switch 4—Installer Test Off/On

Selects a special installer test mode which assists with system

startup and checkout. See Step 5, System Startup and
Check--out.
TO SET:

OFF—for normal operation. This is factory default.
ON—for installer test mode.

STEP 3

Install Thermidistat Control

ELECTRICAL OPERATION HAZARD

Failure to follow this warning could result in personal

injury or death.
Before installing Thermidistat Control, turn off all

power to equipment. There may be more than 1 power

disconnect.

!

WARNING

1. Turn off all power to equipment.

2. If an existing thermostat is being replaced:

a. Remove existing thermostat from wall.

b. Disconnect wires from existing thermostat, 1 at a time.

c. As each wire is disconnected, record wire color and

terminal marking.

d. New or additional wires may be needed to

accommodate added humidity outputs.

e. Discard or recycle old thermostat.

NOTE

: Mercury is a hazardous waste and MUST be disposed of

properly.

3. Select Thermidistat Control rear plastic. (If it is not

separated from the remainder of the Thermidistat Control,
refer to Step 2 above.)

4. Route wires through large hole in rear plastic. Level rear

plastic against wall (for aesthetic value only—Thermidistat

Control need not be leveled for proper operation) and
mark wall through 2 mounting holes.

5. Drill two 3/16--in. mounting holes in wall where marked.
6. Secure rear plastic to wall with 2 screws and anchors

provided. Additional mounting holes are available for

more secure mounting if needed. Make sure all wires
extend through hole in mounting base.

7. Adjust length and routing of each wire to reach proper

connector block and terminal on rear plastic with 1/4--in.
extra length. Strip only 1/4 in. of insulation from each

wire to prevent adjacent wires from shorting together
when connected.

8. Match and connect equipment wires to proper terminals of

each connector block. (See Low Voltage Wiring Diagram
Reference Chart and Figs. 1 through 28 in separate Wiring

Diagram literature.) Remember R and C must be
connected for proper operation. Improper wiring or

installation may damage Thermidistat Control. Check to
make sure wiring is correct before proceeding with
installation or turning on power.

9. Push any excess wire into wall and against rear plastic.

Seal hole in wall to prevent air leaks. Leaks can affect

operation.

10. Reattach Thermidistat Control body to rear plastic by first

reattaching hinge.

11. Close Thermidistat Control assembly, making sure pins on

back of circuit board align with sockets in connector.

12. Turn on power to equipment.

TST

AT

Summary of Contents for THERMIDISTAT CONTROL TSTAT

Page 1: ...r day and 7 days per week The Thermidistat Control can also be field configured as a non programmable thermostat When operating in the non programmable configuration it will still have both temperature and humidity control Humidify and dehumidify outputs provide direct control of humidity Batteries are not used During power loss an internal memory stores programs and settings for unlimited time an...

Page 2: ...mmed temperature at programmed time TO SET OFF for smart recovery This is factory default ON for conventional recovery D Switch 4 Installer Test Off On Selects a special installer test mode which assists with system startup and checkout See Step 5 System Startup and Check out TO SET OFF for normal operation This is factory default ON for installer test mode STEP 3 Install Thermidistat Control ELEC...

Page 3: ... that option One of these will be flashing The up and down buttons are used both to move between available options and to make selection for each option When option number small display is flashing up and down buttons adjust it moving between available option numbers After desired option number has been selected press SET TIME TEMP button once The large display will now flash indicating that up an...

Page 4: ... is done by supplying blower with a Y signal and no G signal on a call for cooling Not all products with ICM blowers have this feature Check Installation Instructions for ICM air handler used Select OF for normal operation Y and G supplied on a cooling call Select ON for super dehumidification Y with no G on a dehumidify only call Factory default is OF off TO SELECT 1 Enter configuration mode if n...

Page 5: ...the desire of indoor comfort TO SELECT 1 Enter configuration mode if not already there See Step 4 To Enter Configuration Mode Use up and down buttons to make small now flashing display indicate 11 2 Press SET TIME TEMP button once to flash large display 3 Use up or down buttons to move between OF 5 10 15 20 25 30 35 40 45 50 or 55 on large display Factory default is OF 4 Press SET TIME TEMP button...

Page 6: ... the 2 operations Specifically to switch from 1 mode to the other there must be no demand for the old mode and a demand for the new mode and this must exist continually for 20 minutes before transition to the new mode will occur TO SELECT 1 Enter configuration mode if not already there See Step 4 To enter Configuration Mode Use up and down buttons to make small now flashing display indicate 14 2 P...

Page 7: ...P button again to flash upper small display for selection of another option or press END to exit configuration mode REDEFINITION OF BUTTONS Fig 2 shows the original programmable button labels on the left and the redefined non programmable buttons on the right In the figure the buttons are numbered for easy reference They are not numbered on the actual product Six of the buttons numbers 1 through 5...

Page 8: ...ent relative humidity is selected by the homeowner or all humidification can be turned off When humidity in home drops below set point humidifier will be turned on to raise humidity level Humidification can only occur in heating mode HEAT or AUTO HEAT Five different humidification selections are available and are described below 1 Normal Humidify In normal humidify humidifier will be on if there i...

Page 9: ...when compressor turns off In most furnaces and fan coils the blower operates for 90 sec after both Y and G disappear This 90 sec delay should be removed if possible for maximum dehumidification performance Consult furnace or fan coil Installation Instructions to see if delay can be disabled 3 Dehumidify Off Dehumidification can be turned off completely This can be done without changing existing se...

Page 10: ...where the DEHUM terminal is a spade lug located next to the transformer secondary connections See Wiring Diagram Reference Chart and Fig 21 through 24 in Wiring Diagram literature When a dehumidify demand exists relay is de energized and normally closed contacts supply 24vac to the furnace DEHUM terminal As a result the furnace control reduces the blower airflow by 15 percent On newer style variab...

Page 11: ...DIFY AND DEHUMIDIFY INDICATORS The humidity screen selected by pressing the HUMIDITY button uses the same triangles referenced in the above paragraph to indicate the state of the HUM and DHUM outputs When humidification or dehumidification is active the triangle under its set point is turned on AUTO CHANGEOVER When auto changeover mode is selected a change from heat to cool or vice versa will not ...

Page 12: ...ontrol cannot properly read outdoor temperature Check outdoor sensor and its wiring E4 or E5 Internal failure Replace Thermidistat Control E6 System is stuck in defrost Check wiring and heat pump defrost control board Clean Filter icon displayed Filter timer has expired Clean or replace filter and then press VACATION and HOLD END buttons together to reset Cooling or heating will not come on See In...

Page 13: ...ctory default Off or Not Available 9 ______ Intelligent Heat Staging Selection Off or On factory default Off or Not Available 10 ______ HybridHeat Equipment Selection Off or On factory default Off or Not Available 11 ______ Balance Point Setting Off or 5 55 F factory default Off or Not Available 12 ______ Defrost Heat Select 0 1 2 3 factory default 0 or Not Available 13 ______ Room Temperature Off...

Page 14: ...orris St S Indianapolis IN 46231 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No II TSTAT 0 38 Replaces II TSTAT 0 27 Printed in U S A Edition Date 04 06 TSTAT ...

Reviews: