Bryant THERMIDISTAT CONTROL TSTAT Installation Instructions Manual Download Page 6

6

3. Use up or down buttons to move between 0, 1, 2, or 3 (if

available) on large display. See Table 1 for effect of these

choices. Factory default is 0.

4. Press SET TIME/TEMP button again to flash upper small

display for selection of another option, or press END to

exit configuration mode.

Option 13—Room Temperature Offset Adjust

This option allows calibration (or deliberate miscalibration) of
room temperature sensor. There are various reasons why

homeowners may want to have displayed temperature adjusted to

a higher or lower value. The selected number is number of
degrees Fahrenheit, plus or minus, which will be added to actual

temperature. The numbers can range between --5 and +5. Factory
default is 0. This adjusted value will be used as actual temperature

for both display and control action. For example, if 2 is selected,
72

_

F actual will read 74

_

F. If set point is 72

_

F, the room will

control to an actual temperature of 70

_

F which will be displayed

and acted upon as if it were 72

_

F. The effect is that a positive

number selection will make the room temperature lower and vice

versa. The Thermidistat Control is calibrated within an accuracy
of plus or minus 1

_

F when shipped from the factory, so this

adjustment will provide the best accuracy when set to 0.
TO SELECT:

1. Enter configuration mode if not already there. See Step 4

“To Enter Configuration Mode.” Use up and down
buttons to make small (now flashing) display indicate 13.

2. Press SET TIME/TEMP button once to flash large display.
3. Use up or down buttons to move between --5, --4, --3, --2,

--1, 0, 1, 2, 3, 4, or 5 on large display. Factory default is 0.

4. Press SET TIME/TEMP button again to flash upper small

display for selection of another option, or press END to
exit configuration mode.

Option 14—Heat/Cool Dead Band Adjustment

This option selects the minimum difference between heat and

cool set points. A larger difference saves energy and a smaller

difference decreases temperature difference between heating and
cooling. Factory default is 2, which means cooling set point must

be a minimum of 2

_

above heating set point. An attempt to move

them closer will result in one “pushing” the other to maintain the

required difference.
Depending on set points, moving dead band closer than 2

_

may

result in regular cycling between heat and cool when AUTO

mode is selected. However, this cycling cannot occur more often
than 1 transition every 20 minutes. The system has a built--in

requirement that it cannot switch between heat and cool without a

20 minute “off” time between the 2 operations. Specifically, to
switch from 1 mode to the other, there must be no demand for the

old mode and a demand for the new mode, and this must exist
continually for 20 minutes before transition to the new mode will

occur.

TO SELECT:

1. Enter configuration mode if not already there. See Step 4

“To enter Configuration Mode.” Use up and down buttons
to make small (now flashing) display indicate 14.

2. Press SET TIME/TEMP button once to flash large display.
3. Use up or down buttons to move between 0, 1, 2, 3, 4, 5,

or 6 on large display. Factory default is 2.

4. Press SET TIME/TEMP button again to flash upper small

display for selection of another option, or press END to

exit configuration mode.

Option 15—Enable Auto Mode

This option allows the installer to enable or disable AUTO mode
(automatic changeover between heat and cool). When disabled,

AUTO icon does not appear when successive presses of MODE
button are used to move between OFF, HEAT, COOL, and

EHEAT (in heat pump systems). Factory default is ON (AUTO

enabled).
TO SELECT:

1. Enter configuration mode if not already there. See Step 4

“To Enter Configuration Mode.” Use up and down

buttons to make small (now flashing) display indicate 15.

2. Press SET TIME/TEMP button once to flash large display.
3. Use up and down buttons to move between OF and ON

on large display. Factory default is ON (AUTO enabled).

4. Press SET TIME/TEMP button again to flash upper small

display for selection of another option, or press END to
exit configuration mode.

Option 16—Enable Super Comfort Heat Mode

This option requires prior ON selection of heat pump (DIP switch

No. 1) and Configuration Option No. 5 (Select Variable--Speed
Blower). Super Comfort Heat mode is part of the Comfort Heat

Pump system, which comprises a selected combination of
Thermidistat Control, variable stage Fan Coil, and 3--stage

electric heater to provide superior heat pump leaving air

temperatures under all conditions. This option selection modifies
heat pump blower and auxiliary heat operation to contribute to

comfortable leaving air temperature. Specifically, this selection
provides:

S

Reduced heat pump airflow for outdoor temperatures between

12

_

and 40

_

F.

S

At least 1 stage of electric heat ON for all heating below 12

_

F.

While outdoor air temperature is between 12

_

F and 40

_

F, the

Thermidistat Control removes the G signal during heat pump
heating. The 40FK, FK4C, or FV4A Variable--Speed Fan Coils

respond by reducing their airflow in the absence of the G signal,
raising leaving air temperature. For any heating demand below

12

_

F, G and W/W1 are turned ON, assuring at least 1 stage of

electric heat is on, and also increasing leaving air temperature.

A99059

Fig. 2

---

Programmable/Non--Programmable Keypad Labels

TST

AT

Summary of Contents for THERMIDISTAT CONTROL TSTAT

Page 1: ...r day and 7 days per week The Thermidistat Control can also be field configured as a non programmable thermostat When operating in the non programmable configuration it will still have both temperature and humidity control Humidify and dehumidify outputs provide direct control of humidity Batteries are not used During power loss an internal memory stores programs and settings for unlimited time an...

Page 2: ...mmed temperature at programmed time TO SET OFF for smart recovery This is factory default ON for conventional recovery D Switch 4 Installer Test Off On Selects a special installer test mode which assists with system startup and checkout See Step 5 System Startup and Check out TO SET OFF for normal operation This is factory default ON for installer test mode STEP 3 Install Thermidistat Control ELEC...

Page 3: ... that option One of these will be flashing The up and down buttons are used both to move between available options and to make selection for each option When option number small display is flashing up and down buttons adjust it moving between available option numbers After desired option number has been selected press SET TIME TEMP button once The large display will now flash indicating that up an...

Page 4: ... is done by supplying blower with a Y signal and no G signal on a call for cooling Not all products with ICM blowers have this feature Check Installation Instructions for ICM air handler used Select OF for normal operation Y and G supplied on a cooling call Select ON for super dehumidification Y with no G on a dehumidify only call Factory default is OF off TO SELECT 1 Enter configuration mode if n...

Page 5: ...the desire of indoor comfort TO SELECT 1 Enter configuration mode if not already there See Step 4 To Enter Configuration Mode Use up and down buttons to make small now flashing display indicate 11 2 Press SET TIME TEMP button once to flash large display 3 Use up or down buttons to move between OF 5 10 15 20 25 30 35 40 45 50 or 55 on large display Factory default is OF 4 Press SET TIME TEMP button...

Page 6: ... the 2 operations Specifically to switch from 1 mode to the other there must be no demand for the old mode and a demand for the new mode and this must exist continually for 20 minutes before transition to the new mode will occur TO SELECT 1 Enter configuration mode if not already there See Step 4 To enter Configuration Mode Use up and down buttons to make small now flashing display indicate 14 2 P...

Page 7: ...P button again to flash upper small display for selection of another option or press END to exit configuration mode REDEFINITION OF BUTTONS Fig 2 shows the original programmable button labels on the left and the redefined non programmable buttons on the right In the figure the buttons are numbered for easy reference They are not numbered on the actual product Six of the buttons numbers 1 through 5...

Page 8: ...ent relative humidity is selected by the homeowner or all humidification can be turned off When humidity in home drops below set point humidifier will be turned on to raise humidity level Humidification can only occur in heating mode HEAT or AUTO HEAT Five different humidification selections are available and are described below 1 Normal Humidify In normal humidify humidifier will be on if there i...

Page 9: ...when compressor turns off In most furnaces and fan coils the blower operates for 90 sec after both Y and G disappear This 90 sec delay should be removed if possible for maximum dehumidification performance Consult furnace or fan coil Installation Instructions to see if delay can be disabled 3 Dehumidify Off Dehumidification can be turned off completely This can be done without changing existing se...

Page 10: ...where the DEHUM terminal is a spade lug located next to the transformer secondary connections See Wiring Diagram Reference Chart and Fig 21 through 24 in Wiring Diagram literature When a dehumidify demand exists relay is de energized and normally closed contacts supply 24vac to the furnace DEHUM terminal As a result the furnace control reduces the blower airflow by 15 percent On newer style variab...

Page 11: ...DIFY AND DEHUMIDIFY INDICATORS The humidity screen selected by pressing the HUMIDITY button uses the same triangles referenced in the above paragraph to indicate the state of the HUM and DHUM outputs When humidification or dehumidification is active the triangle under its set point is turned on AUTO CHANGEOVER When auto changeover mode is selected a change from heat to cool or vice versa will not ...

Page 12: ...ontrol cannot properly read outdoor temperature Check outdoor sensor and its wiring E4 or E5 Internal failure Replace Thermidistat Control E6 System is stuck in defrost Check wiring and heat pump defrost control board Clean Filter icon displayed Filter timer has expired Clean or replace filter and then press VACATION and HOLD END buttons together to reset Cooling or heating will not come on See In...

Page 13: ...ctory default Off or Not Available 9 ______ Intelligent Heat Staging Selection Off or On factory default Off or Not Available 10 ______ HybridHeat Equipment Selection Off or On factory default Off or Not Available 11 ______ Balance Point Setting Off or 5 55 F factory default Off or Not Available 12 ______ Defrost Heat Select 0 1 2 3 factory default 0 or Not Available 13 ______ Room Temperature Off...

Page 14: ...orris St S Indianapolis IN 46231 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No II TSTAT 0 38 Replaces II TSTAT 0 27 Printed in U S A Edition Date 04 06 TSTAT ...

Reviews: