HEAT PUMP HEATING PERFORMANCE

INDOOR

AIR

OUTDOOR COIL ENTERING AIR TEMPERATURES °F

–3

7

17

27

37

47

57

67

EDB

CFM

Capacity

MBtuh†

Total

Pwr

Capacity

MBtuh†

Total

Pwr

Capacity

MBtuh†

Total

Pwr

Capacity

MBtuh†

Total

Pwr

Capacity

MBtuh†

Total

Pwr

Capacity

MBtuh†

Total

Pwr

Capacity

MBtuh†

Total

Pwr

Capacity

MBtuh†

Total

Pwr

Total Int* kW† Total Int* kW† Total Int* kW† Total Int* kW† Total Int* kW† Total Int* kW† Total Int* kW† Total Int* kW†

650A024-D, E Outdoor Section With FX4(A,B)NF030 Indoor Section

65

700

11.1 10.2 1.77 13.5 12.4 1.86 16.0 14.6 1.94 18.6 16.5 2.04 21.6 19.7 2.16 25.0 25.0 2.30 28.9 28.9 2.49 33.2 33.2 2.73

800

11.3 10.4 1.78 13.7 12.6 1.86 16.2 14.7 1.94 18.8 16.7 2.02 21.9 19.9 2.14 25.4 25.4 2.27 29.3 29.3 2.45 33.8 33.8 2.68

900

11.5 10.0 1.80 13.9 12.8 1.87 16.4 14.9 1.94 19.0 16.9 2.02 22.2 20.2 2.13 25.7 25.7 2.26 29.6 29.6 2.43 34.0 34.0 2.61

70

700

10.8 9.95 1.85 13.3 12.2 1.94 15.7 14.3 2.04 18.3 16.2 2.14 21.3 19.4 2.26 24.6 24.6 2.42 28.4 28.4 2.61 32.6 32.6 2.86

800

11.0 10.1 1.86 13.5 12.4 1.95 16.6 15.1 2.04 18.5 16.5 2.12 21.6 19.6 2.24 25.0 25.0 2.38 28.8 28.8 2.56 33.2 33.2 2.80

900

11.2 10.3 1.88 13.7 12.6 1.96 16.1 14.7 2.04 18.7 16.6 2.12 21.8 19.9 2.23 25.3 25.3 2.36 29.2 29.2 2.54 33.6 33.6 2.77

75

700

10.5 9.63 1.93 13.0 12.0 2.03 15.5 14.1 2.14 18.0 16.0 2.24 21.0 19.1 2.37 24.3 24.3 2.53 27.9 27.9 2.73 32.0 32.0 2.98

800

10.7 9.82 1.94 13.2 12.2 2.04 15.7 14.3 2.13 18.3 16.2 2.23 21.2 19.3 2.35 24.6 24.6 2.49 28.4 28.4 2.68 32.6 32.6 2.92

900

10.9 10.0 1.96 13.4 12.4 2.05 15.9 14.5 2.13 18.5 16.4 2.22 21.5 19.6 2.33 24.9 24.9 2.47 28.7 28.7 2.65 33.0 33.0 2.89

Multipliers for Determining the Performance With Other Indoor Sections

Indoor

Section

Size

Heating

Indoor

Section

Size

Heating

Capacity

Power

Capacity

Power

CC5A/CD5AA

036

0.99

0.99

CK5PW

030

0.96

0.97

CC5A/CD5AW

030

0.98

1.05

COILS + 355MAV042040 VARIABLE-SPEED FURNACE

036

1.00

1.00

CC5A/CD5AW

036

0.96

0.96

CE3AA

036

0.98

1.01

COILS + 355MAV042060 VARIABLE-SPEED FURNACE

CF5AA

036

0.99

1.02

CC5A/CD5AA

030

0.94

1.01

CK3BA

036

0.99

0.98

036

0.96

0.97

CK5A/CK5BA

036

0.99

0.98

CC5A/CD5AW

030

0.93

1.00

CK5A/CK5BT

036

0.99

0.98

036

0.96

0.96

CK5A/CK5BW

036

0.99

0.98

CK3BA

036

0.98

0.93

CK5PA

036

0.99

0.98

CK5A/CK5BA

036

0.98

0.93

CK5PT

036

0.99

0.98

CK5A/CK5BT

036

0.98

0.93

CK5PW

036

0.99

0.98

CK5PA

036

0.98

0.93

F(A,B)4BN(F,C)

030

0.98

1.01

CK5PT

036

0.98

0.93

FC4CNF

030

0.98

1.01

COILS + 355MAV042080 VARIABLE-SPEED FURNACE

FE4ANF

002

1.01

0.97

CC5A/CD5AA

036

0.96

0.96

003

1.00

0.96

CC5A/CD5AW

030

0.93

1.00

FK4DNF

001

0.95

0.95

036

0.96

0.96

002

1.00

0.92

CK5A/CK5BW

036

0.97

0.91

003

1.01

0.94

CK5PW

036

0.97

0.91

FV4BNF

002

1.01

0.97

COILS + 355MAV060080 VARIABLE-SPEED FURNACE

003

1.00

0.96

CC5A/CD5AA

036

0.96

0.96

FX4BNF

030

1.00

1.00

CC5A/CD5AW

030

0.93

1.00

COILS + 315(A,J)AV036070 VARIABLE-SPEED FURNACE

036

0.96

0.96

CC5A/CD5AA

030

0.93

0.98

COILS + 355MAV060100 VARIABLE-SPEED FURNACE

036

0.96

0.95

CC5A/CD5AA

036

0.96

0.96

CC5A/CD5AW

030

0.93

0.98

CC5A/CD5AW

030

0.93

0.99

CK3BA

030

0.94

0.94

036

0.96

0.96

CK5A/CK5BW

030

0.94

0.94

CK5A/CK5BW

036

0.99

0.91

CK5PA

030

0.96

0.97

CK5PW

036

0.99

0.91

036

0.99

0.96

COILS + 355MAV060120 VARIABLE-SPEED FURNACE

CK5PT

036

0.99

0.96

CC5A/CD5AW

036

0.96

0.97

See notes on page 32.

Summary of Contents for QUANTUM PLUS 650A

Page 1: ...frequency sound and pres sure pulsation generated by compressor discharge gas WEATHER PROTECTIVE CABINET The casing steel is galva nized and coated with a layer of zinc phosphate A layer of modified p...

Page 2: ...7 8 DIA HOLE WITH 1 1 8 DIA KNOCKOUT AND 1 3 8 DIA KNOCKOUT 10 1 2 FIELD CONTROL SUPPLY CONN 1 9 16 C F 2 15 16 G A B M DIMENSIONS IN UNIT SIZE SERIES UNIT DIMENSIONS MINIMUM MOUNTING PAD DIMENSIONS...

Page 3: ...DIAMETER IN VAPOR TUBE DIAMETER IN 0 to 50 Ft Tube Length 0 to 50 Ft Tube Length 0 to 50 Ft Alternate 024 3 8 5 8 3 4 ACR 030 3 8 3 4 5 8 7 8 036 3 8 3 4 5 8 7 8 042 048 3 8 7 8 3 4 7 8 060 3 8 1 1 8...

Page 4: ...d 18 In KHASS0206MPK Time Delay Relay KAATD0101TDR Ball Bearing Fan Motor HC38GE231 RCD MotorMaster Low Ambient Controller KSALA0401AAA Outdoor Thermostat KHAOT0301FST Secondary Outdoor Thermostat KHA...

Page 5: ...266 295 ELECTRICAL Unit Volts Hertz Phase 208 230 60 1 Operating Voltage Range 187 253 Compressor Rated Load Amps 21 1 20 5 21 8 27 6 Compressor Locked Rotor Amps 104 0 109 0 117 0 158 0 Condenser Fa...

Page 6: ...rogrammable F C 2 Stage Heat 1 Stage Cool Heat Pump TSTATBBBHP01 Outdoor Air Temperature Sensor TSTATXXSEN01 B Backplate for Non Programmable Thermostat TSTATXXNBP01 Backplate for Programmable Thermos...

Page 7: ...lled at the outdoor unit to control refrigerant off cycle migration in the heating mode Usage Guideline An LLS is required in all long line heat pump applications to control refrigerant off cycle migr...

Page 8: ...g pad This allows sand dirt and other debris to be flushed from the unit base minimizing corrosion Usage Guideline Suggested in the following applications Coastal installations Windy areas or where de...

Page 9: ...CC5A CD5AA030 23 400 TDR 13 20 11 75 23 400 3 06 15 000 2 26 7 5 CC5A CD5AA036 24 200 TDR 14 00 12 10 24 000 3 28 15 200 2 36 7 8 CC5A CD5AW030 23 400 TDR 13 20 11 75 23 200 3 06 15 000 2 26 7 5 CC5A...

Page 10: ...0 28 600 3 48 17 200 2 40 7 8 CC5A CD5AW036 28 600 TDR 14 00 12 30 28 600 3 50 17 200 2 40 7 8 CK5A CK5BW036 29 200 TDR 14 00 12 35 28 800 3 74 17 900 2 52 8 0 CK5PW036 29 200 TDR TXV 14 00 12 35 28 8...

Page 11: ...5 36 000 3 64 22 200 2 60 8 5 CK5A CK5BA048 34 600 TDR 14 00 11 55 36 000 3 70 22 600 2 68 8 8 CK5A CK5BT042 34 400 TDR 13 50 11 45 35 800 3 64 22 200 2 60 8 5 CK5A CK5BT048 34 600 TDR 14 00 11 55 36...

Page 12: ...8 33 400 TDR 13 50 11 15 35 200 3 34 22 400 2 52 8 0 CC5A CD5AW042 33 400 TDR 13 50 11 15 35 200 3 36 22 400 2 52 8 0 CC5A CD5AW048 34 000 TDR 13 50 11 35 35 400 3 56 22 600 2 58 8 5 CD5AA048 34 000 T...

Page 13: ...3 50 11 25 40 500 3 32 25 200 2 46 7 5 CD5AA048 40 000 TDR 13 50 11 25 40 500 3 32 25 200 2 46 7 5 CE3AA048 40 500 TDR 13 50 11 15 40 500 3 36 25 400 2 48 7 6 CK3BA048 40 000 TDR 13 50 11 20 40 500 3...

Page 14: ...10 90 48 000 3 54 28 600 2 38 8 1 FX4BNF048 45 000 TDR TXV 12 50 10 75 48 000 3 42 28 400 2 34 8 0 COILS 315 A J AV048090 VARIABLE SPEED FURNACE CE3AA060 44 500 TDR 13 00 11 40 47 500 3 64 27 400 2 50...

Page 15: ...800 2 44 8 3 CK5PA060 45 000 TDR TXV 13 00 11 25 47 000 3 50 27 800 2 40 8 2 CK5PT060 45 000 TDR TXV 13 00 11 25 47 000 3 50 27 800 2 40 8 2 CK5PX060 45 500 TDR TXV 13 50 11 45 47 500 3 54 27 800 2 44...

Page 16: ...MPERATURE F 10 0 10 20 30 40 50 60 70 80 2 9 5 9 8 8 11 7 14 7 17 6 20 5 70 60 50 40 30 20 10 kW BASED ON INDOOR ENT AIR AT 70 F AND AT RATED CFM 23 4 80 650AN BALANCE POINT WORKSHEET 650AN024 E FX4A0...

Page 17: ...8 17 4 2 89 19 1 16 7 3 19 62 25 9 24 7 1 92 24 7 24 1 2 13 23 5 23 3 2 37 22 3 22 3 2 62 21 1 21 1 2 89 19 7 19 7 3 19 57 25 5 25 5 1 91 24 5 24 5 2 13 23 4 23 4 2 37 22 3 22 3 2 62 21 1 21 1 2 89 1...

Page 18: ...31 0 2 17 29 7 29 7 2 41 28 3 28 3 2 68 26 8 26 8 2 98 25 1 25 1 3 31 23 2 23 2 3 67 57 31 0 31 0 2 17 29 7 29 7 2 41 28 3 28 3 2 68 26 8 26 8 2 98 25 1 25 1 3 31 23 2 23 2 3 67 Multipliers for Deter...

Page 19: ...7 9 4 48 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CC5A CD5AA 042 0 99 1 02 CK5A CK5B...

Page 20: ...27 9 4 48 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CK3BA 042 1 00 0 93 CK5PA 042 0...

Page 21: ...0 8 40 8 3 34 39 0 39 0 3 74 37 1 37 1 4 19 35 1 35 1 4 68 32 8 32 8 5 20 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling...

Page 22: ...4 14 34 2 34 2 4 62 32 0 32 0 5 15 1575 72 50 0 26 7 3 04 47 7 25 9 3 41 45 3 25 1 3 81 42 7 24 2 4 26 39 9 23 2 4 74 36 8 22 2 5 26 67 46 0 34 7 3 00 43 9 33 9 3 37 41 6 33 0 3 77 39 3 32 1 4 22 36 7...

Page 23: ...ndoor Section Size Cooling Capacity Power Capacity Power CC5A CD5AA 060 0 98 1 07 CK5PA 060 0 98 0 98 CC5A CD5AW 060 0 98 1 05 CK5PT 060 0 98 0 98 CD5PX 060 0 98 1 03 CK5PX 060 1 00 0 99 CE3AA 060 1 0...

Page 24: ...4 37 1 7 30 62 59 2 55 1 4 29 56 4 53 7 4 78 53 5 52 3 5 33 50 5 50 4 5 93 47 5 47 5 6 60 44 2 44 2 7 32 57 57 8 57 8 4 27 55 6 55 6 4 77 53 1 53 1 5 32 50 5 50 5 5 93 47 5 47 5 6 60 44 2 44 2 7 32 20...

Page 25: ...15 9 14 5 2 13 18 5 16 4 2 22 21 5 19 6 2 33 24 9 24 9 2 47 28 7 28 7 2 65 33 0 33 0 2 89 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Heating Indoor Sect...

Page 26: ...4 1 2 36 18 6 16 9 2 41 21 9 19 5 2 45 25 7 23 4 2 51 30 1 30 1 2 58 35 0 35 0 2 67 40 6 40 6 2 81 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Heating In...

Page 27: ...3 48 50 3 50 3 3 71 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Heating Indoor Section Size Heating Capacity Power Capacity Power CC5A CD5AA 042 0 99 1 0...

Page 28: ...W 048 0 98 0 95 CK5A CK5BT 042 0 92 0 97 COILS 315 A J AV066155 VARIABLE SPEED FURNACE 048 0 92 0 94 CC5A CD5AW 042 0 96 0 98 CK5PA 042 0 99 1 00 048 0 96 0 94 048 0 98 0 99 CD5AA 048 0 95 0 94 CK5PT...

Page 29: ...h Other Indoor Sections Indoor Section Size Heating Indoor Section Size Heating Capacity Power Capacity Power CC5A CD5AC 048 1 00 1 11 CK5A CK5BT 048 1 00 0 98 CC5A CD5AW 048 1 01 1 07 CK5A CK5BW 048...

Page 30: ...6 3 66 56 9 56 9 4 00 75 1225 16 2 14 9 2 88 20 6 18 9 3 03 25 1 22 8 3 19 29 3 26 0 3 34 34 3 31 2 3 51 39 9 39 9 3 73 46 7 46 7 4 01 54 6 54 6 4 39 1400 16 5 15 2 2 88 20 9 19 2 3 02 25 3 23 1 3 17...

Page 31: ...00 CC5A CD5AW 060 1 01 1 06 CK5PX 060 1 00 0 99 CD5PX 060 0 98 1 10 COILS 315 A J AV066155 VARIABLE SPEED FURNACE CE3AA 060 1 01 1 06 CC5A CD5AW 060 0 99 1 08 CK3BA 060 1 01 1 03 CE3AA 060 0 99 1 02 C...

Page 32: ...rmance With Other Indoor Sections Indoor Section Size Heating Indoor Section Size Heating Capacity Power Capacity Power CC5A CD5AW 060 0 98 1 06 COILS 315 A J AV066110 VARIABLE SPEED FURNACE CD5PX 060...

Page 33: ...33...

Page 34: ...34...

Page 35: ...35...

Page 36: ...d of galvanized steel bonderized and coated with a powder coat paint Fans Condenser fan will be direct drive propeller type discharging air upward Air Cooled Split System Heat Pump 650A 2 to 5 Tons No...