—24—
DETAILED COOLING CAPACITIES* Continued
NOTE: When the required data fall between the published data, interpolation may be performed. Extrapolation is not an acceptable practice.
* Detailed cooling capacities are based on indoor and outdoor unit at the same elevation per ARI standard 210/240-94. If additional tubing length and/or
indoor unit is located above outdoor unit, a slight variation in capacity may occur.
† Total and sensible capacities are net capacities. Blower motor heat has been subtracted.
‡ Sensible capacities shown are based on 80°F (27°C) entering air at the indoor coil. For sensible capacities at other than 80°F (27°C), deduct 835 Btuh
(245 kW) per 1000 CFM (480 L/S) of indoor coil air for each degree below 80°F (27°C), or add 835 Btuh (245 kW) per 1000 CFM (480 L/S) of indoor coil air
per degree above 80°F (27°C).
** System kW is total of indoor and outdoor unit kilowatts.
†† At TVA rating indoor condition (75°F edb/63°F ewb). All other indoor air temperatures are at 80°F edb.
EWB—Entering Wet Bulb
EVAP
AIR
CONDENSER ENTERING AIR TEMPERATURES °F
75
85
95
105
115
125
CFM
EWB
Capacity
MBtuh†
Total
Sys
kW**
Capacity
MBtuh†
Total
Sys
kW**
Capacity
MBtuh†
Total
Sys
kW**
Capacity
MBtuh†
Total
Sys
kW**
Capacity
MBtuh†
Total
Sys
kW**
Capacity
MBtuh†
Total
Sys
kW**
Total Sens‡
Total Sens‡
Total Sens‡
Total Sens‡
Total Sens‡
Total Sens‡
650AN060-D, E Outdoor Section With FV4(A,B)NB006 Indoor Section
1750
72
70.1
35.6
4.43
66.6
34.4
4.92
63.1
33.1
5.47
59.2
31.7
6.07
55.0
30.3
6.73
50.2
28.7
7.42
67
64.4
45.5
4.35
61.3
44.2
4.85
58.0
42.9
5.40
54.5
41.5
6.00
50.6
40.0
6.65
46.4
38.4
7.35
63†† 60.2
44.3
4.30
57.2
43.0
4.79
54.2
41.7
5.34
50.9
40.3
5.94
47.3
38.8
6.60
43.4
37.1
7.30
62
59.2
55.1
4.29
56.4
53.7
4.78
53.5
52.3
5.33
50.5
50.4
5.93
47.5
47.5
6.60
44.2
44.2
7.32
57
57.8
57.8
4.27
55.6
55.6
4.77
53.1
53.1
5.32
50.5
50.5
5.93
47.5
47.5
6.60
44.2
44.2
7.32
2000
72
71.1
37.4
4.52
67.6
36.1
5.02
63.9
34.8
5.57
59.8
33.4
6.16
55.5
32.0
6.81
50.6
30.4
7.51
67
65.5
48.5
4.44
62.2
47.2
4.94
58.8
45.9
5.49
55.1
44.4
6.09
51.1
42.9
6.74
46.8
41.2
7.44
63†† 61.2
47.1
4.39
58.1
45.8
4.88
54.9
44.4
5.43
51.6
43.0
6.03
47.9
41.5
6.68
43.8
39.7
7.39
62
60.5
59.0
4.38
57.7
57.4
4.88
54.9
54.9
5.43
52.1
52.1
6.04
48.9
48.9
6.70
45.3
45.3
7.42
57
60.1
60.1
4.38
57.6
57.6
4.88
54.9
54.9
5.43
52.1
52.1
6.04
49.0
49.0
6.70
45.4
45.4
7.42
2250
72
72.0
39.1
4.61
68.3
37.8
5.10
64.4
36.5
5.65
60.4
35.1
6.25
55.9
33.7
6.90
50.8
32.0
7.59
67
66.2
51.4
4.53
62.9
50.1
5.03
59.4
48.7
5.57
55.6
47.3
6.17
51.7
45.7
6.83
47.1
43.9
7.53
63†† 61.9
49.8
4.48
58.8
48.5
4.97
55.6
47.1
5.52
52.1
45.6
6.12
48.3
44.0
6.77
44.1
42.1
7.48
62
61.8
61.8
4.48
59.2
59.2
4.98
56.5
56.5
5.53
53.5
53.5
6.14
50.2
50.2
6.80
46.4
46.4
7.51
57
61.8
61.8
4.48
59.2
59.2
4.98
56.4
56.4
5.53
53.4
53.4
6.14
50.2
50.2
6.80
46.4
46.4
7.51
Multipliers for Determining the Performance With Other Indoor Sections
Indoor
Section
Size
Cooling
Indoor
Section
Size
Cooling
Capacity
Power
Capacity
Power
CC5A/CD5AW
060
0.97
0.99
COILS + 315(A,J)AV066110 VARIABLE-SPEED FURNACE
CD5PX
060
0.97
1.02
CD5PX
060
0.97
1.00
CK5A/CK5BX
060
0.97
0.99
COILS + 315(A,J)AV066155 VARIABLE-SPEED FURNACE
CK5PX
060
0.97
0.99
CC5A/CD5AW
060
0.97
0.98
FB4BNB
070
0.98
1.04
COILS + 355MAV060080 VARIABLE-SPEED FURNACE
FC4CNB
070
0.98
1.04
CD5PX
060
0.96
1.04
FE4ANB
006
1.00
1.00
COILS + 355MAV060100 VARIABLE-SPEED FURNACE
FK4DNB
006
1.00
1.00
CD5PX
060
0.97
1.03
FV4BNB
006
1.00
1.00
COILS + 355MAV060120 VARIABLE-SPEED FURNACE
FX4BNB
060
0.98
1.04
CD5PX
060
0.95
1.00