GUIDE SPECIFICATIONS

GENERAL

System Description

Outdoor--mounted, air--cooled, split--system air conditioner

unit suitable for ground or rooftop installation. Unit consists

of a hermetic compressor, an air--cooled coil, propeller--type
condenser fan, and a control box. Unit will discharge supply

air upward as shown on contract drawings. Unit will be used
in a refrigeration circuit to match up to a packaged fan coil

or coil unit.

Quality Assurance

— Unit will be rated in accordance with the latest edition of

AHRI Standard 210.

— Unit will be certified for capacity and efficiency, and listed

in the latest AHRI directory.

— Unit construction will comply with latest edition of ANSI/

ASHRAE and with NEC.

— Unit will be constructed in accordance with UL standards

and will carry the UL label of approval. Unit will have
c--UL approval.

— Unit cabinet will be capable of withstanding Federal Test

Method Standard No. 141 (Method 6061) 500--hr salt

spray test.

— Air--cooled condenser coils will be leak tested and pressure

tested.

— Unit constructed in ISO9001 approved facility.

Delivery, Storage, and Handling

— Unit will be shipped as single package only and is stored

and handled per unit manufacturer’s recommendations.

Warranty (for inclusion by specifying engineer)

— U.S. and Canada only.

PRODUCTS

Equipment

— Factory assembled, single piece, air--cooled air conditioner

unit. Contained within the unit enclosure is all factory

wiring, piping, controls, compressor, refrigerant charge
Puron

r

(R--410A), and special features required prior to

field start--up.

Unit Cabinet

— Unit cabinet, including louvered coil guard, will be

constructed of galvanized steel, bonderized, and coated
with a powder coat paint.

Fans

— Condenser fan will be direct--drive foward--swept

propeller type, discharging air upward.

AIR--COOLED, SPLIT--SYSTEM AIR CONDITIONER

186B

1--1/2 TO 5 NOMINAL TONS

— Condenser fan motors will be totally enclosed, 1--phase

type with class B insulation and permanently lubricated
bearings. Shafts will be corrosion resistant.

— Fan blades will be statically and dynamically balanced.
— Condenser fan openings will be equipped with coated steel

wire safety guards.

Compressor

— Compressor will be hermetically sealed.
— Compressor will be mounted on rubber split--post vibration

isolators.

— Compressor will be covered with a sound absorbing

blanket.

Condenser Coil

— Condenser coil will be air cooled.
— Coil will be constructed of aluminum fins mechanically

bonded to copper tubes which are then cleaned,
dehydrated, and sealed.

Refrigeration Components

— Refrigeration circuit components will include liquid--line

back--seating shutoff valve with sweat connections,
vapor--line back--seating shutoff valve with sweat

connections, system charge of Puron

r

(R--410A)

refrigerant, and compressor oil.

— Unit will be equipped with high--pressure switch, low

pressure switch and filter drier for Puron refrigerant.

Operating Characteristics

— The capacity of the unit will meet or exceed _____ Btuh at

a suction temperature of _____

_

F/

_

C. The power

consumption at full load will not exceed _____ kW.

— Combination of the unit and the evaporator or fan coil unit

will have a total net cooling capacity of _____ Btuh or
greater at conditions of _____ CFM entering air
temperature at the evaporator at _____

_

F/

_

C wet bulb and

_____

_

F/

_

C dry bulb, and air entering the unit at _____

_

F/

_

C.

— The system will have a SEER of _____ Btuh/watt or

greater at DOE conditions.

Electrical Requirements

— Nominal unit electrical characteristics will be _____ v,

single phase, 60 hz. The unit will be capable of satisfactory

operation within voltage limits of _____ v to _____ v.

— Unit electrical power will be single point connection.
— Control circuit will be 24v.

Special Features

— Refer to section of this literature identifying accessories

and descriptions for specific features and available

enhancements.

186B

Summary of Contents for EVOLUTION 16 186B

Page 1: ...e ratings information INDUSTRY LEADING FEATURES BENEFITS Efficiency S 14 16 SEER 11 0 13 5 EER S Microtube Technologyt refrigeration system S Indoor air quality accessories available Sound S Sound level as low as 68 dBA S Compressor sound blanket standard Comfort S System supports Evolution Control or standard thermostat controls Reliability S Puronr refrigerant environmentally sound won t deplete...

Page 2: ... X X X X X Internal Thermal Overload X X X X X X X X Long Line capability X X X X X X X X Low Ambient capability with Kit X X X X X X X X High Pressure Switch X X X X X X X X Low Pressure Switch X X X X X X X X Compressor Sound Blanket X X X X X X X X Louvered Coil Guard X X X X X X X X Based on tested combinations X Standard PHYSICAL DATA UNIT SIZE SERIES 018 A 024 A 030 A 036 A 042 A 048 A 060 A...

Page 3: ...50 250 250 250 250 230 160 060 061 AC with Puron 3 8 3 8 250 250 250 225 190 150 110 Maximum actual length not to exceed 200 ft 61 m Total equivalent length accounts for losses due to elbows or fitting See the Long Line Guideline for details outside acceptable range Maximum Total Equivalent Length Outdoor Unit ABOVE Indoor Unit Size Liquid Line Connection Liquid Line Diam w TXV AC with Puron Refri...

Page 4: ... 4 No accessories needed within allowed lengths No accessories needed within allowed lengths 175 53 3 5 16 120 36 6 50 15 2 vertical or 120 36 6 total 120 36 6 3 8 80 24 4 35 10 7 vertical or 80 24 4 total 80 24 4 Note See Long Line Guideline for details VAPOR LINE SIZING AND COOLING CAPACITY LOSS Acceptable vapor line diameters provide adequate oil return to the compressor while avoiding excessiv...

Page 5: ...Optional wall control used to monitor temperature and or fan control in an individual zone SYSTXBBRRS01 Evolution Remote Room Sensor Monitors temperature in an individual zone SYSTXBBRWF01 Evolution System Access Module Hardware for wireless access and control via phone or internet SYSTXBBNIM01 Evolution Network Interface Module Connects Heat Recovery and Energy Recovery Ventilators on non zoning ...

Page 6: ...to 0_F 18_C when properly installed Usage Guideline A Low Ambient Pressure Switch or MotorMasterr Low Ambient Controller must be used when cooling operation is used at outdoor temperatures below 55_F 12 8_C 7 Outdoor Air Temperature Sensor Designed for use with Bryant Thermostats listed in this publication This device enables the thermostat to display the outdoor temperature This device also is re...

Page 7: ... consult applicable tables of the NEC NFPA 70 Length shown is as measured one way along wire path between unit and service panel for voltage drop not to exceed 2 Time Delay fuse FLA Full Load Amps LRA Locked Rotor Amps MCA Minimum Circuit Amps RLA Rated Load Amps NOTE Control circuit is 24 V on all units and requires external power source Copper wire must be used from service disconnect to unit Al...

Page 8: ...15 16 5 8 17 16 3 4 14 200 243 186B042 A X O O O 35 40 1 4 3 7 8 7 8 6 9 16 28 7 16 9 1 8 2 15 16 5 8 17 16 18 1 2 253 297 186B048 A X O 0 0 35 40 1 4 3 7 8 7 8 6 9 16 28 7 16 9 1 8 2 15 16 5 8 17 1 2 16 1 4 18 295 340 186B060 A X O 0 0 35 47 1 16 3 7 8 7 8 6 9 16 28 7 16 9 1 8 2 15 16 5 8 17 1 2 17 1 4 21 327 373 5 186B061 A X O O O 35 47 1 16 3 7 8 7 8 6 9 16 28 7 16 9 1 8 2 15 16 5 8 17 1 4 17 ...

Page 9: ... 913 2 186B036 A X O 0 0 889 0 763 9 97 9 22 2 166 1 722 8 231 3 74 5 16 3 431 8 425 5 355 6 90 7 110 2 917 7 X 997 7 X 913 2 186B042 A X O O O 889 0 1022 9 97 9 22 2 166 1 722 8 231 3 74 5 16 3 431 8 406 4 469 9 114 8 134 7 917 7 X 997 7 X 1172 2 186B048 A X O 0 0 889 0 1022 9 97 9 22 2 166 1 722 8 231 3 74 5 16 3 444 5 412 8 457 2 133 8 154 2 917 7 X 997 7 X 1172 2 186B060 A X O 0 0 889 0 1195 7...

Page 10: ...6 Service 24 609 6 Service 24 609 6 Service 24 609 6 24 609 6 24 609 6 12 304 8 12 304 8 12 304 8 12 304 8 6 152 4 Note Numbers in mm IMPORTANT When installing multiple units in an alcove roof well or partially enclosed area ensure there is adequate ventilation to prevent re circulation of discharge air 186B ...

Page 11: ...5 186BNA061 A CNPV 6124A TDR 59 500 12 0 14 5 AHRI Air Conditioning Heating Refrigeration Institute EER Energy Efficiency Ratio SEER Seasonal Energy Efficiency Ratio TDR Time Delay Relay In most cases only 1 method should be used to achieve TDR function Using more than 1 method in a system may cause degradation in performance Use either the accessory Time Delay Relay KAATD0101TDR or a furnace equi...

Page 12: ...18 57 18 57 1 17 17 82 17 82 1 31 17 03 17 03 1 46 16 18 16 18 1 62 15 27 15 27 1 80 14 30 14 30 2 01 EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES F C 75 23 9 85 29 4 95 35 105 40 6 115 46 1 125 51 7 CFM EWB F C Capacity MBtuh Total Sys KW Capacity MBtuh Total Sys KW Capacity MBtuh Total Sys KW Capacity MBtuh Total Sys KW Capacity MBtuh Total Sys KW Capacity MBtuh Total Sys KW Total Sens Tot...

Page 13: ... 96 3 49 72 22 2 29 80 29 80 1 94 28 59 28 59 2 17 27 34 27 34 2 43 25 99 25 99 2 73 24 53 24 53 3 08 22 93 22 93 3 49 EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES F C 75 23 9 85 29 4 95 35 105 40 6 115 46 1 125 51 7 CFM EWB F C Capacity MBtuh Total Sys KW Capacity MBtuh Total Sys KW Capacity MBtuh Total Sys KW Capacity MBtuh Total Sys KW Capacity MBtuh Total Sys KW Capacity MBtuh Total Sys ...

Page 14: ...72 22 2 43 29 43 29 2 77 41 94 41 94 3 11 40 42 40 42 3 52 38 73 38 73 3 98 36 87 36 87 4 50 34 82 34 82 5 09 EVAPORATOR AIR CONDENSER ENTERING AIR TEMPERATURES F C 75 23 9 85 29 4 95 35 105 40 6 115 46 1 125 51 7 CFM EWB F C Capacity MBtuh Total Sys KW Capacity MBtuh Total Sys KW Capacity MBtuh Total Sys KW Capacity MBtuh Total Sys KW Capacity MBtuh Total Sys KW Capacity MBtuh Total Sys KW Total ...

Page 15: ...door Section With CNPV 6124A TDR Indoor Section 1750 72 22 2 68 26 35 40 3 65 65 62 34 24 4 19 62 70 33 02 4 80 59 44 31 72 5 50 55 84 30 35 6 31 51 84 28 89 7 25 67 19 4 62 16 43 65 3 59 59 80 42 52 4 12 57 18 41 32 4 72 54 27 40 05 5 42 51 03 38 69 6 24 47 43 37 23 7 18 63 17 2 57 75 41 99 3 55 55 60 40 87 4 07 53 20 39 69 4 67 50 52 38 42 5 37 47 55 37 07 6 18 44 22 35 62 7 13 62 16 7 56 92 51 ...

Page 16: ...2 42 40 4 44 TCG 24 60 23 70 22 70 21 60 20 40 19 10 17 80 16 30 SDT 68 40 77 90 87 30 96 70 106 10 115 50 124 80 134 10 KW 0 95 1 12 1 29 1 46 1 66 1 88 2 13 2 42 45 7 22 TCG 27 10 26 00 24 90 23 70 22 40 21 10 19 60 18 00 SDT 69 60 79 00 88 30 97 60 107 00 116 30 125 60 134 90 KW 0 94 1 11 1 29 1 47 1 67 1 89 2 14 2 43 50 10 0 TCG 29 70 28 60 27 30 26 00 24 60 23 10 21 50 19 80 SDT 70 80 80 10 8...

Page 17: ...1 3 83 4 42 40 4 44 TCG 39 90 39 00 37 90 36 60 35 00 33 20 31 10 28 90 SDT 72 70 81 90 91 20 100 40 109 60 118 70 127 80 136 90 KW 1 63 1 87 2 15 2 49 2 88 3 33 3 85 4 45 45 7 22 TCG 43 90 42 90 41 60 40 10 38 40 36 40 34 20 31 80 SDT 74 20 83 30 92 50 101 60 110 80 119 90 128 90 137 90 KW 1 64 1 88 2 17 2 51 2 91 3 36 3 88 4 48 50 10 0 TCG 48 10 46 90 45 50 43 90 42 00 39 80 37 40 34 80 SDT 75 8...

Page 18: ...0 129 90 138 60 KW 2 18 2 54 2 90 3 28 3 69 4 15 4 66 5 25 186BNA061000BAAA 30 1 11 TCG 47 40 46 30 45 00 43 40 41 50 39 30 36 80 33 80 SDT 70 70 80 00 89 20 98 50 107 70 116 90 126 00 135 10 KW 1 95 2 35 2 79 3 30 3 90 4 61 5 45 6 46 35 1 67 TCG 52 30 51 10 49 60 47 90 45 90 43 40 40 70 37 40 SDT 72 20 81 40 90 60 99 70 108 90 118 00 127 00 136 00 KW 1 98 2 38 2 82 3 34 3 94 4 65 5 49 6 49 40 4 4...

Page 19: ... 1 2 TO 5 NOMINAL TONS Condenser fan motors will be totally enclosed 1 phase type with class B insulation and permanently lubricated bearings Shafts will be corrosion resistant Fan blades will be statically and dynamically balanced Condenser fan openings will be equipped with coated steel wire safety guards Compressor Compressor will be hermetically sealed Compressor will be mounted on rubber spli...

Page 20: ...nt distributor 6 If any refrigerant tubing is buried provide a 6 in 152 4 mm vertical rise to the valve connections at the unit Refrigerant tubing lengths up to 36 in 914 4 mm may be buried without further consideration Do not bury refrigerant lines longer than 36 in 914 4 mm 7 Use only copper wire for electric connection at unit Aluminum and clad aluminum are not acceptable for the type of connec...