Bryant ERVBBLHU1150 Installation, Start-Up, And Operating Instructions Manual Download Page 8

Total cu ft. X 0.3 per hr = total. Take total and divide by 60 to get
CFM.

Example:

1320 sq ft. x 8ft in height = 10560 cu ft house

10560 cu ft X 3 floors = 31680 total cu ft in house

31680 cu ft X 0.3 air change per fr = 9500 cu ft

9500 cu ft

÷

60 minimum per hr = 160 CFM

Conclusion: The total amount of airflow needed is 160 CFM. This
falls within airflow range of a ERVCCLHU1200 size unit.

CONTROL BOARD OPERATION

I.

BOARD FUNCTION

To ensure proper operation of ERV, configuration jumpers are
located on electronic control board and must match configuration
setup shown on Fig. 16 under Jumper Table. Jumpers are factory
set and do not require any changes unless control board is replaced.
If control board is replaced, or unusual start-up operation is
encountered, check jumpers to make sure they are located properly
(See Fig. 16).

II.

DEFROST

Defrost cycle is controlled by a thermistor which is located in the
fresh-air intake passage (the thermistor unit is connected to J4 of
control module (See Fig. 16). When defrost temperature sensor
detects the need for defrost, K5 relay will close for 6 minutes while
K1 and K2 remain energized.

This closes the outdoor air damper while running ERV blower on
high-speed. This process recirculates warm indoor air through heat
recovery core which melts any frost that has formed. Water created
in this process is collected by ERV and drained away. Frequency
of the defrost cycle depends on outdoor temperature (See Table 3).

III.

OFF AND INTERMITTENT/OFF MODE

Whenever ERV is off, K1 relay is open (See Fig. 16).

IV.

HIGH-SPEED AIR EXCHANGE

When high-speed air exchange occurs, K1 relay closes and K2
(12–vdc relay) is energized. This breaks low-speed contacts, and
closes high-speed contacts. Then, 115vac is applied between
orange and grey wires on Molex plug (pins 1 and 6) and motor
runs in high-speed operation. Also, 115vac is applied across pins
5 and 7, this energizes interlock relay (See Fig. 16).

Fig. 11–Push Button Timer Layout

A98386

3

4

5

I

OC

OL

YELLOW

BLACK

RED

ELECTRONIC CONTROL  
BOARD

BACK OF PUSH BUTTON SWITCH

J3

J1

6

7

8

9

4

1

7

5

2

8

6

3

9

BLACK – (J3-4)

COMMON

TERMINAL

STRIP

YELLOW – (J3-3)

INDICATOR
TERMINAL  STRIP

RED – (J3-5)

SWITCH
TERMINAL  STRIP

BLACK – 

COMMON, (J3-4)

YELLOW – 

INDICATOR, (J3-3)

THE  WIRES  FROM  THE  SWITCH

RED – 

SWITCH, (J3-5)

(OC)

(I)

(OL)

(OPTIONAL)

60 MINUTE TIMER

(OPTIONAL)

PUSH BUTTON SWITCHES

(5 SWITCHES MAXIMUM)

—8—

Summary of Contents for ERVBBLHU1150

Page 1: ...able during start up and adjustment procedures and service calls Recognize safety information This is the safety alert symbol When you see this symbol on the furnace and in instructions or manuals be...

Page 2: ...etween the 2 airstreams 6 Blowers bring in fresh air from outside and exhaust stale air to outside 7 Electronic control circuit board ensures proper operation of unit 8 Fresh air supply connected to r...

Page 3: ...il will energize See Fig 10 and interlock relay kit for additional information and Installation Instructions NOTE The fresh air from ERV is introduced into return air duct at a point no less than 6 ft...

Page 4: ...inside of building is higher than setpoint then no air exchange will occur and ERV shuts off If relative humidity level inside building is lower than setpoint then air exchange occurs at high speed a...

Page 5: ...n timers that can be applied is 5 III 60 MINUTE ADJUSTABLE TIMER A 60 minute adjustable timer can also be used to override wall control and put ERV into high speed operation for a select amount of tim...

Page 6: ...installed as close to the ERV as possible and in straightest sections of duct to ensure accuracy See Fig 12 If only one flow collar is available install collar in stale air duct of the ERV and record...

Page 7: ...Building Code 1990 version and the CSA F326 1 revision The following 2 methods can be used to evaluate the approximate ventilation needs of a house Accuracy of calculations are depen dent upon the inf...

Page 8: ...lose for 6 minutes while K1 and K2 remain energized This closes the outdoor air damper while running ERV blower on high speed This process recirculates warm indoor air through heat recovery core which...

Page 9: ...low this caution may result in personal injury Sheet metal parts may have sharp edges or burrs Use care and wear appropriate protective clothing and gloves when handling parts Fig 12 Balancing ERVBBLH...

Page 10: ...OTING WARNING ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death Before installing or servicing system always turn off main power to system There may be mo...

Page 11: ...wire from control board 2 Take ohm reading across thermistor 3 Refer to Table 4 for temperature ohm relationship OPERATING THE ERV WITH THE EVOLUTION CONTROL The ERV may be controlled using the Evolut...

Page 12: ...INAL WIRE AS SUPPLIED MUST BE REPLACED USE THE SAME OR EQUIVALENT WIRE 5 FACTORY SET WIRING FOR BLOWER SPEED SELECTION IS HIGH AND LOW MEDIUM SPEED CAN BE SELECTED INSTEAD OF LOW SPEED DISCONNECT RED...

Page 13: ...ll control Is in defrost Wait until de frost has termi nated maximum of 40 minutes Broken control wire Test wall con trol check con nections check thermistor Unit stops mo mentarily Electrical supply...

Page 14: ...6 993 94 6 661 96 6 368 98 6 085 100 5 811 102 5 571 104 5 313 106 5 088 108 4 869 110 4 660 112 4 450 114 4 268 116 4 019 118 3 918 120 3 750 TABLE 6 FACTORY SET BLOWER CONNECTION HIGH OR LOW SPEED...

Page 15: ...15...

Page 16: ...2005 Bryant Heating Cooling Systems 7310 W Morris St Indianapolis IN 46231 16 Printed in U S A erv643 Catalog No II ERV 64 3...

Reviews: